FUNCTIONS
62
HEATING CLIMATIC CURVES (K7 AND K8)
15
25
35
45
55
65
-30
-20
-10
0
10
20
30
K7
K8
OAT (°C)
Setpoint dell'acqua (°
C)
— If the OAT is valid (not transmitted by the inverter, value out
of range, etc.), the water setpoint is equal to the maximum
current water temperature.
— If the OAT is above the maximum current OAT threshold, the
water setpoint is equal to the minimum current water temper-
ature.
The climatic curve corresponds to the water setpoint for the Home
mode. To define the other occupation modes, it is necessary to
configure the Night heating offset [P402] and the Away heating off
-
set[P403]:
HEATING CLIMATIC CURVES RELATED TO WORKING MODE HOME
5
15
25
35
45
55
65
-40
-30
-20
-10
0
10
20
30
Home
Sleep
Away
P403
P402
WSP (°
C)
OAT (°C)
Fixed water setpoint
If the cooling climate curve [P586] or the heating climate curve
[P581] are configured to "-1", the water control point will be de
-
termined based on the occupation mode, with direct access to the
control panel.
The water setpoint with direct access to the control panel (refer to
the user manual of the control panel)
COOLING
Control panel
occupation
Water setpoint with direct access to the control panel
Field
Water setpoint from the parameter menu
Field
Cooling setpoint home
5 - 18°C
Cooling setpoint home [P407]
5 - 18°C
Cooling setpoint night
5 - 18°C
Cooling setpoint home [P407] + night cooling offset [P408]
0 - 10°C
Cooling setpoint away
5 - 18°C
Cooling setpoint home [P407] + away cooling offset [P409]
0 - 10°C
HEATING