FUNCTIONS
64
Example:
CUSTOMIZED HEATING CLIMATIC CURVES
5
15
25
35
45
55
65
-40
-30
-20
-10
0
10
20
30
P585
P582
P583
P584
min
Default
max
OAT (°C)
WSP (°C
)
— If the OAT is not valid, the water setpoint is equal to the max-
imum personalized water temperature [P585].
— If the OAT is above the maximum current OAT threshold, the
water setpoint is equal to the minimum personalized water
temperature [P584].
— If the minimum OAT is greater than or equal to the current
maximum OAT threshold, the water setpoint is equal to the
customized minimum water temperature [P584].