19
2.9
Electrical connection
N
GND
1
2
3
4
5
6
7
8
9
10
Sensor
230 V
11
12
13
14
15
16
17
18
19
20
21
22
A3
A2
A1 (n)
L1
N
T1
T2
L1’
/
Top
L1’
PWM
Pump A1
PWM
Pump A2
F2
2
F3
F4
F5
G
F1
5
Fig. 2.5
Power supply:
230V AC - Relay contact ratings (2) A 250V AC
Network connections:
2
Phase wire (device power supply L)
1
Neutral wire, device
N
Neutral wire, pump A1
5
Phase wire A2 (power supply to valve
/ pump / additional heater)
6
Phase wire (power supply to pump A1)
N
Neutral wire, valve / pump / additional
heater A2/A3
9
Phase wire (power supply to valve /
pump / additional heater A3)
Place a jumper between 2-3
Place a jumper between 3-10
Place a jumper between 1 and neutral
terminal N
11-12
PWM pump A1
13-14
PWM pump A2
15-GND
probe F1
17-GND
probe F2
18-19 o GND
probe F3
20-GND
probe F4
21-GND
probe F5
22-GND
Pulse transmitter
Place a jumper between 16 and GND
Place a jumper between 19 and GND
F1 = temperature probe F1
F2 = temperature probe F2
F3 = temperature probe F3
F4 = temperature probe F4
F5 = temperature probe F5
P30 = parameter 30
Switching conditions:
e.g.
ON: F1 - F4 > P30 and F1 > P40
(temperature F1 minus temperature F4
greater than parameter 30 and tem-
perature F1 greater than parameter
P40)
OFF: F1 - F4 < P31 or F1 < P41 (tempera-
ture F1 minus temperature F4 less
than parameter P31 or temperature F1
less than parameter P41)
b
Sensor:
The sensor in the collector must
be type KLF 1000 (cable with silicone
sheath). For all other applications, type
SPF 1000 can also be used.
b
For the electrical connections (230V),
flexible wires must be used with prop-
erly attached ferrule cable ends.
b
The BUS wires and sensor lines must be
laid separately from the network wires!