background image

27

TECHNICAL ASSISTANCE CENTRE

13  CHECKS DURING AND AFTER INITIAL START-UP

On completion of the installation, perform the checks listed in the table below.

Checking the solar collector circuit

CHECK THAT THE SOLAR COLLECTOR CIRCUIT HAS BEEN PROPERLY BLED
THERE ARE NO CONNECTIONS BETWEEN THE SOLAR HEATING CIRCUIT AND OTHER WATER 

SUPPLIES

External water supplies such as automatic filling systems can alter the strength of the water-glycol mix 

and lead to serious frost damage.
THE PROPYLENE GLYCOL DELIVERED WITH THE COLLECTORS HAS BEEN USED TO MAKE THE 

WATER-GLYCOL ANTI-FREEZE MIX

It is essential to use the non-toxic, biodegradable and environmentally friendly propylene glycol supplied 

with the collectors. The use of other types of anti-freeze mix can damage the solar water heating system 

because other products form residues and deposits at high temperatures.
THE PERCENTAGE OF GLYCOL IN THE MIX IS BETWEEN 30% AND 50%

The percentage of glycol in the anti-freeze mix must be adjusted to suit the minimum temperature 

expected in the place of installation. 50% glycol provides anti-freeze protection down to -32°C. Higher 

percentages can cause the mix to become too dense.
THE DENSITY OF THE HEAT TRANSFER LIQUID IS BETWEEN 1.029 AND 1.045 kg/dm

3

Use an instrument like a refractometer or densimeter to check the density of the anti-freeze. Excessively 

dense mixes cause solid deposits to form at high temperatures and prevent proper circulation. 

Insufficiently dense mixes expose the system to the risk of freezing.
THE pH OF THE HEAT TRANSFER LIQUID IS HIGHER THAN 7

Use litmus paper to ensure that the pH of the mix is not too acid. This check is not necessary when the 

system is started up for the first time, but becomes necessary after the system has been operating for 

more than 2 years. If the mix becomes acidic, then the heat transfer liquid will be corrosive.
THE SAFETY VALVE OPERATES AT 6 BAR AND CANNOT BE SHUT OFF BY ANY COCKS

The percentage of glycol in the anti-freeze mix must be adjusted to suit the minimum temperature 

expected in the place of installation. 50% glycol provides anti-freeze protection down to -32°C. Higher 

percentages can cause the mix to become too dense
CHECK THAT ALL THE PIPES IN THE WATER CIRCUIT HAVE BEEN INSULATED IN CONFORMITY TO 

RELEVANT STANDARDS
INITIAL PRESSURE IN THE SOLAR COLLECTOR CIRCUIT

Check that the pressure in the circuit, when cold, is 1.5 bar at the collector field. Low pressure leads to 

lower evaporation temperatures in the collectors during the stagnation phase. The evaporation point must 

be kept high.
THE FLOW RATE THROUGH THE CIRCUIT IS 0.5 l/min FOR EVERY m

2

 OF COLLECTOR AREA

Adjust the flow regulator to achieve a flow rate of 0.5 l/min for every m

2

 of collector area. For example, if 

you have a total of 5 m

2

 of collector area, flow rate must be 2.5 - 3 l/min.

CHECK THAT THE TEMPERATURE DIFFERENTIAL BETWEEN THE COLLECTOR OUTLET AND RETURN 

IS BETWEEN 10°C AND 25°C

When the solar circuit is functioning, the temperature differential between the collector outlet and the 

return should be between 10°C and 25°C.

Temperature controller checks

THE COLLECTOR TEMPERATURE SENSOR IS CORRECTLY POSITIONED AT THE COLLECTOR OUTLET

The collector temperature sensor must be installed at the outlet from the last collector in the series. The 

socket for the temperature sensor is located on the left hand side of the collectors supplied with the 

system. Make sure that the cold water return leads to the right hand side of the collectors and that the 

temperature sensor is installed in the socket in the left of the leftmost collector in the series.
THE STORAGE CYLINDER TEMPERATURE SENSOR IS CORRECTLY POSITIONED IN THE SOCKET AT 

THE BOTTOM OF THE STORAGE CYLINDER

The storage cylinder temperature sensor must be installed to measure water temperature at the bottom of 

the storage cylinder.
THE ‘PUMP ON’ ΔT BETWEEN THE COLLECTOR AND THE STORAGE CYLINDER IS BETWEEN 6 AND 

10 °C

The temperature differential between the collectors and the storage cylinder that switches on the 

circulation pump must be in the range between 6 and 10°C. If the differential is set too low, the circulation 

pump will keep cycling on and off. If the temperature differential is set too high, the efficiency of the 

system will be reduced.
THE ‘PUMP OFF’ ΔT BETWEEN THE COLLECTOR AND THE STORAGE CYLINDER IS BETWEEN 2 AND 

4 °C

The Δt off temperature differential serves to stop the circulation pump cycling on and off.
MAXIMUM STORAGE CYLINDER TEMPERATURE IS BETWEEN 60 AND 80° C.E191

Set storage cylinder temperature to the maximum permitted on the basis of water hardness.
MINIMUM COLLECTOR TEMPERATURE IS BETWEEN 15 AND 20 °C

Set the minimum collector temperature to suit minimum outdoor temperature and so that the temperature 

controller receives the signal somewhere in the range between 15 and 20°C.

Summary of Contents for FKB-SOL 200/1

Page 1: ...Installation Manual Solar forced circulation system FKB SOL Installation Manual EN...

Page 2: ...e observed to ensure the trouble free installation and efficient functioning of your B forced circulation system Please accept our renewed thanks for your purchase Beretta CONFORMITY B storage cylinde...

Page 3: ...bleed valve available as an accessory 11 7 3 IDRA FI LE solar storage cylinder 11 7 3 1 System layout 12 7 3 2 Technical specifications 13 7 3 3 Storage cylinder water circuit 14 7 3 4 Overall dimens...

Page 4: ...he mains electricity supply if a supplementary heating element is installed shut off the water supply and notify B s Technical Assistance Service or a qualified heating engineer immediately b b Make s...

Page 5: ...lves and the complete system are identified by Data plate The B FKB SOL solar water heating system is identified by system data plates marked with the code description and serial number of the product...

Page 6: ...ssory 3 B IDRA FI LE solar storage cylinder 4 Outlet temperature gauge 5 Valve M 6 Return temperature gauge 7 CONTROL BOX SUN B solar controller 8 Flow regulator 9 Expansion vessel 10 Sensor power cab...

Page 7: ...W Annual non solar heat contribution Qnonsol M 1000 790 kWh a L 1975 1345 kWh a XL 3439 2509 kWh a XXL 4573 3508 kWh a Annual auxiliary electricity consumption Qaux 138 138 kWh a Value calculated in...

Page 8: ...Total area 2 30 m2 Exposed area 2 16 m2 Effective absorption area 2 15 m2 Connections M F 1 mm Empty weight 40 0 kg Liquid content 1 6 l Recommended flow rate for each line per m2 of collector 30 l h...

Page 9: ...lector and the surrounding air and with total solar radiation of 1000 W m2 referred to the exposed area WIND AND SNOW LOADS ON COLLECTORS Installation height above ground Wind speed Mass in kg to secu...

Page 10: ...ther in series provided each line contains no more than 6 collectors or in parallel The complete circuit must always be hydraulically balanced See the following sample layouts Two lines in series Two...

Page 11: ...old is higher than 26 C replace the mix or add anti freeze as required Use litmus paper to check the pH nominal value approx 7 5 If the measured value is below 7 change the heat transfer liquid 7 3 ID...

Page 12: ...nsulation 11 Boiler temperature sensor socket 12 Valve group 13 Storage cylinder 14 Plug for anode inspection and lifting 15 Fitting for pipe from solar collector 16 Outlet valve M 17 Outlet temperatu...

Page 13: ...operating pressure of coils 10 bar Maximum operating temperature 99 C Net weight 105 130 kg Heat loss according to EN 12897 2006 at T 45 C 74 69 W Energy efficiency class C B Useful non solar volume...

Page 14: ...Expansion vessel 3 Flow meter 4 Central heating system pump 5 Valve R functions as non return valve 6 Temperature gauge 7 Pressure gauge 8 Safety valve 6 bar 9 Heat transfer fluid recovery 10 Valve M...

Page 15: ...om solar collector 1 M R Return to solar collector 1 M RL DHW recirculation 3 4 F EAF SB Domestic cold water inlet storage cylinder drain 1 F Psc Diameter length of boiler sensor socket 16 175 mm Psr...

Page 16: ...R Return to solar collector 1 M RL DHW recirculation 3 4 F EAF SB Domestic cold water inlet storage cylinder drain 1 F Psc Diameter length of boiler sensor socket 16 175 mm Psr Diameter length of sola...

Page 17: ...17 GENERAL 7 4 Pump Residual head Water outlet and return group RESIDUAL HEAD mbar 800 700 600 500 400 300 0 200 400 600 800 FLOW RATE l h Tests performed with water at 20 C Flow regulator fully open...

Page 18: ...ar controller Heat is only transferred from the solar collector circuit to the storage cylinder when the temperature of the solar collectors exceeds that of the water in the storage cylinder It is the...

Page 19: ...DHW circulation EAF Domestic cold water inlet SB Storage cylinder drain Note The above schematic is purely indicative b b The domestic hot water system MUST INCLUDE an expansion vessel safety valve au...

Page 20: ...lat seal rings 1 located in the corner profiles of each collector b b This instruction manual is an integral part of the FKB SOL system Once located read it thoroughly and keep it safe b b STORE IN A...

Page 21: ...espect to the heat exchange coil inlet and outlet and mark the points to drill for the expansion plugs b b To avoid damage make holes in the storage cylinder insulation at the points marked before ins...

Page 22: ...tected against damage by the weather and birds and animals Angle of collectors General Solar collectors are designed to be installed at angles of between 15 minimum and 75 maximum Make sure that the b...

Page 23: ...o terminal strip MO1 in the solar controller terminals 1 2 GND Refer to the solar controller s own manual for details On completion of the electrical connections close the cover E of the solar control...

Page 24: ...w slot is horizontal b b If copper piping has been used and joints have been hot brazed flush out the system to remove any brazing residues Seal test the system after you have flushed it out b b Fill...

Page 25: ...sity 50 32 C 1 045 kg dm3 40 21 C 1 037 kg dm3 30 13 C 1 029 kg dm3 b b The propylene glycol supplied is specially formulated for solar collector applications and remains fully efficient throughout th...

Page 26: ...sure in the system to 4 bar Start up the system for about 20 minutes Bleed the circuit again from step 2 until all the air has been removed Set the circuit pressure according to the table on the next...

Page 27: ...N THE SOLAR COLLECTOR CIRCUIT Check that the pressure in the circuit when cold is 1 5 bar at the collector field Low pressure leads to lower evaporation temperatures in the collectors during the stagn...

Page 28: ...lity over time Have your storage cylinder serviced either by the manufacturer s Technical Assistance Centre or by a qualified heating engineer at least once a year Perform the following operations bef...

Page 29: ...node plug to a torque of 25 30 Nm 1 2 3 Cleaning inside the storage cylinder Remove the screws 4 Remove the flange cover 5 Remove the insulation 6 Unscrew the bolts 7 and remove the cover 8 Remove the...

Page 30: ...ure that the hot water outlet is from the left of the collector field The pump gets switched on very late and stops soon afterwards giving no time for proper heat transfer The temperature differential...

Page 31: ...31 TECHNICAL ASSISTANCE CENTRE...

Page 32: ...oilers com Beretta reserves the right to modify the characteristics and specifications given in this publication at any time and without prior notice as part of its policy of continuous product improv...

Reviews: