12 PLACE OF INSTALLATION
B
IDRA MS FI LE
storage cylinders can be installed
in any room where there is no specific requirement for an
electrical protection rating higher than IP X0D.
b
Respect the minimum specified installation distances
to ensure correct installation and access for mainte-
nance.
≥ 0,4 m
≥ 0,6 m
≥ 0,3 m
≥ 0,4 m
13 INSTALLATION IN OLDER
SYSTEMS AND SYSTEMS
REQUIRING MODERNISATION
When installing
B
IDRA MS FI LE
storage cylinders in
old systems or systems requiring modernisation, always
perform the following checks.
- Make sure that the system is fitted with safety and
control devices in accordance with applicable legis-
lation and standards
- Make sure that the central heating circuit has been
flushed out to remove all sludge and lime scale, and
has been vented and seal tested
- Make sure that a suitable water treatment system is
installed if the quality of the supply/recirculation water
so demands (refer to the reference values listed in the
table alongside).
REFERENCE VALUES
pH
6-8
Electrical conductivity
less than 200 μS/cm (25°C)
Chlorine ions
less than 50 ppm
Sulphuric acid ions
less than 50 ppm
Total iron
less than 0.3 ppm
Alkalinity M
less than 50 ppm
Total hardness
less than 35°F
Sulphur ions
none
Ammonia ions
none
Silicon ions
less than 30 ppm
14 PREPARING FOR INITIAL
STARTUP
- Connect the safety valve drain to a pipe (T) to avoid
burns from expelled fluid and to permit the heat trans-
fer fluid to be recovered
- Connect up an expansion vessel (E) designed for use
in solar water heating systems
- Connect the pump and the sensors to the solar con-
troller (if provided) as instructed in the manual sup-
plied with the controller.
SAFETY
DRAIN
T
E