USER MANUAL 1.10 | DC1000 DIALOG-CONTROLLER
Berghof Automation GmbH | Harretstrasse 1 | 72800 Eningen | www.berghof.com
DC1000_HB_en_2D0982010ZD00.docx | 2VF100124FE08.docx
112
2VF100464DG01.cdr
Input voltage (DC) of extern power supply
U
e
24 V
Rated voltage
U
e
max.
30 V
Upper limit
U
e
min.
19.2 V
Lower limit
Limits for “1” signal for the “ON” condition
UH
max.
30.0 V
Upper voltage limit
IH
max.
5.2 mA
Upper current limit
UH
min.
11.0 V
Lower voltage limit
IH
min.
1.5 mA
Lower current limit
Limits for “0” signal for the “OFF” condition
UL
max.
5.0 V
Upper voltage limit
IL
max.
0.8 mA
Upper current limit
UL
min.
0 V
Lower voltage limit
IL
min.
0 mA
Lower current limit
U max.
e
UH max.
IH max.
IH min.
U = 24 VDC
e
U min.
e
5,0
10,0
15,0
20,0
25,0
30,0
U [V]
0,0
0,00
1,00
2,00
3,00
4,00
5,00
6,00
7,00
8,00
9,00
10,00
11,00
[mA]
I
UH min.
UL min.
UL max.
IL max.
IL min.
'ON' / HIGH - area
noise margin < 1 V
cross-over area
noise margin < 1 V
'OFF' / LOW - area
Operating ranges
of the digital inputs