Performing a functional test
The functional test must be carried out at regular intervals.
Recommendation: 1 x per month
The operating voltage is connected.
Switch on residual-current circuit-breaker with push-button ((a), Figure 1).
Voltage is present at the downstream socket-outlets and loads.
Press test button
T
((b), Figure 1).
Figure 2
The residual current circuit-breaker trips and the push-button moves to the “Off” position
(Figure 2). Downstream socket outlets/loads are de-energised. The functional test has been
passed.
or:
The residual current circuit-breaker does not trip and the push-button remains in the “On”
position (Figure 2).Residual-current circuit-breaker is now ready for operation.
Replace the residual-current circuit-breaker and repeat the functional test.
Information for electricians
Installation and electrical connections
DANGER!
Touching live parts can result in an electric shock!
An electric shock can be lethal!
Disconnect the connecting cables before working on the device and cover all
live parts in the area!
ç
The wiring must be adapted to the existing power mains. Check the power mains before any
wiring work.
Off
Desconectado
Av
On
Conectado
På