Testing the safeguards
The safeguard must be tested in accordance with the valid regulations for installation.
Determine earthing resistance.
Maximum permissible touch voltage
Maximum permissible earthing resistance
at rated fault current 30 mA
25 V
833 Ω
50 V
1666 Ω
The maximum permissible earthing resistance must not be exceeded.
Appendix
Technical Data
Rated voltage
230 V~, 50/60 Hz
Rated current
16 A
Rated fault current
30 mA
Short-circuit resistance
3 kA
(with back-up fuse 16 A gl)
Operating temperature
-25 ... +40 °C
Connection cable
1.5 ... 2.5 mm
2
Troubleshooting
The residual-current circuit-breaker trips during operation.
Cause: Connected devices are faulty.
Check connected devices and exchange if necessary.
Accessories
Centre plate for residual-current circuit-breaker
1496 ..
Intermediate ring for centre plate 50 x 50 mm
1108 .., 1109 ..
Warranty
We reserve the right to make technical and formal changes to the product in the interest of tech-
nical progress.
Our products are under guarantee within the scope of the statutory provisions.
If you have a warranty claim, please contact the point of sale or ship the device postage free
with a description of the fault to the appropriate regional representative.