5 Information for electricians
5.1 Installation and electrical connection
DANGER!
Touching live parts in the installation environment can result in
an electric shock.
An electric shock can lead to death.
Disconnect the connecting cables before working on the device
and cover all live parts in the area!
ç
Preparing installation
As a display and operating panel, the device should be mounted in a place
that is easily accessible. The user habits are decisive when determining the
installation height. We recommend an installation height from the display/hous-
ing centre to the fi nished fl oor of approx. 1.65 m.
Direct sunlight or powerful light sources
could impair the brightness sensor.
Prevent humidity and excessive dust at the installation location. Do not
install the device near heat sources, such as radiators, storage heaters or
ovens.
The touch panel must be installed in a separately available fl ush-mounted
housing (see accessories).
CAUTION!
Damage to the device if installed in a warped housing.
The device can be damaged.
When installing the housing in a wall, ensure that the wall
opening is big enough and the device can be inserted without
without tensions.
ç
Information concerning the installation of the fl ush-mounted housing in
solid and hollow walls can be referred to in the instructions enclosed.
To avoid EMC interference, do not install network input cables parallel to
mains cables.
z
19
Summary of Contents for 7574 01 07
Page 27: ...z 27...