English
31
5.3.2
Setting the closing and opening type of end of travel
This section shows the option for the actuator’s end of travel setting
in both direction (Open and Close):
Position
or
Torque
can be
selected.
How to set the closing and opening type
1.
Enter the menu, then go to
Settings
>
Actuator
commissioning
>
Closing & Opening type
.
2.
Select your option with
or
on the right knob then confirm
with
OK
on the left knob.
3.
Select
Save
then validate with
OK
on the left knob.
5.3.3
Setting the torque limits
This setting allows to set torque
limits at the main steps of the
travel: at the beginning (
Break
),
during the travel (
Run
) and at
the end of the travel (
End
).
Limits are:
•
In closing direction:
Break to Close (
BTC
), Run to
Close (
RTC
), End to Close
(
ETC
), Tight zone
•
In opening direction:
Break to Open (
BTO
), Run to
Open (
RTO
), End to Open (
ETO
), Tight zone
To ensure unseating, the Break percentage should be
superior to the Tight zone percentage.
Summary of Contents for AT LOGIC v2
Page 1: ...AT LOGIC v2 RANGE Start Up Guide SUG_17011_EN Ind E Art 5100582 ...
Page 2: ......
Page 71: ......