  ACyCLIC COmmUNICATION 

The INTELLIBUS supports acyclic communication (extension V1 of the Profibus protocol) which  

allows to read the actuator’s state, to read all its configuration. It can be also reconfigured through 

the V1 extension.

There is two type of master in the acyclic communication:

-  The master class1 which supports cyclic communication. It is normally the same PLC which 

manages the actuators.

-  The master class2 supports all the acyclic communication. It can be included to Profibus  

without interference. A laptop equipped with a Profibus module and PDM software may be used  

as a master class2 anywhere on the line.

The INTELLIBUS supports the Read and Write messages  

of the master class1 (MSAC1_Read, MSAC1_Write).

For master class 2, this interface supports Initiate, 

Abort, Read and Write services. Interface board supports  

a maximum of 2 simultaneous class2 master connections.

We advise to use PDM Siemens software to read and 

configurate the actuators with a master class2. We can 

give you an Electronic Device Description (EDD) which 

allows you to manage our actuators with PDM.

With PDM and this EDD you can configure and parameterise  

the actuators and also recover information for diagnostics  

and maintenance.

For example, alarms, activity, torque curves…

To use PDM, not straight to the fieldbus but above  

the PLC then the PLC must be Siemens S7 400 series.

In case of a redundant system, the connection of PDM 

to one fieldbus line, will collect all data including those 

communicating on the other line.

  AvAILABLE DATA THROUgH PROFIBUS ACyCLIC COmmUNICATION 

Data is organised in slot and index:

Slot = 0

Indexes (0 to 61)are listed below.

Index

Data

Description

Byte

Read/write

0

Set-up for auxiliary  

command 1

0: not used

1:local(0) / remote(1)

2:local+remote(0) / remote(1)

3:local command inhibit(1)

4:open inhibit(1)

5:close inhibit(1)

6:ON-OFF(0) / AUTO(1)

7:fieldbus emergency closing (1)

8: fieldbus emergency opening (1)

9: fieldbus emergency stop (1)

10: partial stroke (1)

1

read / write

1

Set-up for auxiliary  

command 2 coming  

through the fieldbus  

but for emergency commands 

wired separately from  

the fieldbus.

0: not used

1:local(0) / remote(1)

2:local+remote(0) / remote(1)

3:local command inhibit(1)

4:open inhibit(1)

5:close inhibit(1)

6:ON-OFF(0) / AUTO(1)

7: wired emergency closing (1)

8: wired emergency opening (1)

9: wired emergency stop (1)

10: partial stroke (1)

1

read / write

2

Local stop also inhibited  

with a local command inhibit

0: no, local stop is possible

1: yes, local stop and off inhibited

1

read / write

3

Timing control

0: no timing control

1: timing control

1

read / write

4

no local stop in remote mode

0= local stop possible

1= no local stop

1

read / write

5

open priority

0= no priority

1= open priority

1

read / write

6

close priority

0= no priority 

1= close priority

1

read / write

7

In case of emergency  

command, torque limit is 100% 0= no, 1= yes

1

read / write

8

In case of emergency 

command, thermal overload

is by- passed

0= no, 1= yes

1

read / write

9

Fail safe position in case  

of loss of communication

0= stayput

1= closing

2= opening

1

read / write

10

Dead band for positioner 

function

Unit 0.1% 

mini value: 2  (0.2%)

maxi value: 50 (5%)

1

read / write

11

Start of closing  

temporised zone

0 to100 %

1

read / write

Profibus

DPV1

Ethernet

PLC

PDM

PDM

Summary of Contents for Intellibus

Page 1: ...instructions for start up INTELLIBUS PROFIBUS DP FOR INTELLI Intelli 2801 A1150 ...

Page 2: ...ring RedCom with redundancy extensions that can be used if the PLC can support the same extensions According to the fieldbus version required an INTELLIBUS single or redundant line may equip the actuator Control box with inside Profibus DP interface could be supplied to connect other equipment Please make sure to get and read the INTELLI instructions for start up ref NR1151 prior going further wit...

Page 3: ... cross Redundant channel No data exchange empty square Channel 1 is primary and on data exchange rotating triangle Channel 2 is backup and on data exchange alternative up and down triangle Channel 1 Intellibus module fault blinking cross Channel 2 is primary and on data exchange rotating triangle 3 2 Cabletype Use exclusively special PROFIBUS cable conforms to the EN50170 2 standard and of type A ...

Page 4: ...s on No ramifications 3 6 Emergencysupply The actuator INTELLI is normally supplied by the mains but in case of loss of power supply an emergency supply could be used to continue to communicate through the fieldbus This emergency supply needs 24V DC 4W 3 7 ProfibusDParchitecture Single line The Profibus cable coming from the PLC is connected to the first actuator then the Profibus cable links this...

Page 5: ...ommunication The cyclic communication is mainly use for the Process Data are read and written in a well defined timing The useful data are selected in the list below and transmitted in a cyclic way The selection of only a few data also increases the communication speed The acyclic communication is mainly use for maintenance The data are collected only on request that avoid to reduce the cyclic com...

Page 6: ... between proportional and ON OFF control assign an auxiliary command to the function AUTO ON OFF then select the control mode required from the control room see above Address 1 Address 4 Relay output option The relays could be used to have an output indication wired as a non fieldbus actuator or to drive outside devices through Profibus These optional relays could be configured in Intelli menu for...

Page 7: ...g closing direction of rotation discrepant BATTERY LOW OR IS NOT PRESENT In case of battery option the battery should be replaced because of too low voltage or the battery is missing Address 3 Running torque in RUNNING TORQUE Indication of the instantaneous torque 100 is the maximum actuator rated torque Address 4 Actuator position feedback ACTUATOR POSITION FEEDBACK 0 closed 100 open Bit n Value ...

Page 8: ... Bit n Value Description Bit 0 0 NO INDICATION 1 1 INDICATION 1 IS ACTIVE OPTION Bit 1 0 NO INDICATION 2 1 INDICATION 2 IS ACTIVE OPTION Bit 2 0 NO INDICATION 3 1 INDICATION 3 IS ACTIVE OPTION Bit 3 0 NO INDICATION 4 1 INDICATION 4 IS ACTIVE OPTION Bit 4 0 NO INDICATION 5 1 INDICATION 5 IS ACTIVE ESD INPUT BY DEFAULT Bit 5 0 NO VALVE JAMMED ALARM 1 VALVE JAMMED Bit 6 0 NO AUXILIARY 24V FAULT ALARM...

Page 9: ...ures since actuator manufacturing Address 18 to 21 Running time TOTAL RUNNING TIME To obtain the accumulated figures since actuator manufacturing Unit is 1 10 sec Address 22 to 25 Partial number of starts PARTIAL NUMBER OF STARTS Number of starts since the last reset Address 26 to 29 Partial running time PARTIAL RUNNING TIME Total running time since the last reset Unit is 1 10 sec Address 30 and 3...

Page 10: ...er line AvailabledatathroughPROFIBUSacycliccommunication Data is organised in slot and index Slot 0 Indexes 0 to 61 are listed below Index Data Description Byte Read write 0 Set up for auxiliary command 1 0 not used 1 local 0 remote 1 2 local remote 0 remote 1 3 local command inhibit 1 4 open inhibit 1 5 close inhibit 1 6 ON OFF 0 AUTO 1 7 fieldbus emergency closing 1 8 fieldbus emergency opening ...

Page 11: ...torque curve Torque in Data 1 closed position Data 2 1 open Data 101 100 open 101 read only Index Data Description Byte Read write 39 Closing torque curve Torque in Data 1 closed position Data 2 1 open Data 101 100 open 101 read only 40 Profibus slave address 1 125 1 read only 41 Indication address 0 Replicate the data of the cyclic register 1 read only 42 Indication address 1 Replicate the data o...

Page 12: ... 4 39 80 726 MOROCCO AQUATEL sarl aquatel wanadoo net ma CASABLANCA Tel 212 22 66 55 71 NETHERLANDS BERNARD CONTROLS BENELUX NV hans nobels bernardcontrols com AN ZWAAG Tel 31 0 229 298083 NEW ZEALAND MRCTransmark NZ LTD bill sunley mrctransmark com Auckland Tel 64 9 276 4149 NORWAY KSB LINDFLATEN AS firmapost lindflaten no LYSAKER Tel 476 71 29 900 POLAND MARCO matzanke pol pl WARSAW Tel 48 22 86...

Reviews: