background image

14

15

Address 5 :Hardwired inputs (option) and Intellibus indication 

(*)The connection depends of actuator type. Refer to the actuator wiring diagram

INDICATION 1 to 4 IS ACTIVE (option): Indications of hardwired inputs (allows to communicate 

through Profibus, indications coming from outside devices).

INDICATION 5 IS ACTIVE: By default this terminal is assigned to a hardwired emergency command 

(ESD) and an ESD command is present.

JAMMED VALVE: Actuation could not be completed due to excess torque.

AUXILIARY 24V FAULT: Auxiliary power supply fault for external circuits 

TOO MANY STARTS: Starting rate exceeding the actuator class average.

Address 6 :

ACTUATOR PUMPING: positioning is unstable

CONFIGURATION/ACTIVITY/BASE FAULT: memory fault

STOP MID TRAVEL: The actuator is at a stop, neither open nor closed.

LOST SIGNAL: 4 to 20mA lost signal (In case of analogue and hardwired  input signal)

PARTIAL STROKE IN PROGRESS: A partial stroke command has been issued and this test is not 

ended.

PARTIAL STROKE FAULT: The partial stroke test has detected a fault. The actuator is not fully 

available.

Address 7 :

Bit n°

Value

Description

Bit 0

0

NO INDICATION 1

1

INDICATION 1 (*) IS ACTIVE (OPTION)

Bit 1

0

NO INDICATION 2

1

INDICATION 2 (*) IS ACTIVE (OPTION)

Bit 2

0

NO INDICATION 3

1

INDICATION 3 (*) IS ACTIVE (OPTION)

Bit 3

0

NO INDICATION 4 

1

INDICATION 4 (*) IS ACTIVE (OPTION)

Bit 4

0

NO INDICATION 5

1

INDICATION 5 (*) IS ACTIVE (ESD INPUT BY DEFAULT)

Bit 5

0

NO VALVE JAMMED ALARM

1

VALVE JAMMED 

Bit 6

0

NO AUXILIARY 24V FAULT ALARM

1

AUXILIARY 24V FAULT

Bit 7

0

NO ALARM TOO MANY STARTS

1

TOO MANY STARTS

Bit n°

Value

Description

Bit 0

0

NO PUMPING 

1

ACTUATOR PUMPING

Bit 1

0

NO CONFIGURATION MEMORY FAULT

1

CONFIGURATION MEMORY FAULT

Bit 2

0

NO ACTIVITY MEMORY FAULT

1

ACTIVITY MEMORY FAULT

Bit 3

0

NO BASE MEMORY FAULT

1

BASE MEMORY FAULT

Bit 4

0

NO STOP MID TRAVEL

1

STOP MID TRAVEL

Bit 5

0

NO LOST SIGNAL

1

LOST SIGNAL

Bit 6

0

NO PARTIAL STROKE IN PROGRESS

1

PARTIAL STROKE IN PROGRESS

Bit 7

0

NO PARTIAL STROKE FAULT

1

PARTIAL STROKE FAULT

Bit n°

Value

Description

Bit 0

0

CHANNEL IS BACKUP (REDUNDANCY OPTION)

1

CHANNEL IS PRIMARY (REDUNDANCY OPTION)

Bit 1

0

1 CHANNEL AVAILABLE (REDUNDANCY OPTION)

1

2 CHANNELS AVAILABLE (REDUNDANCY OPTION)

Bit 2

0

SR MODE (SYSTEM REDUNDANCY) (REDUNDANCY OPTION)

1

FR MODE (FLYING REDUNDANCY)   (REDUNDANCY OPTION)

Bit 3

0

NO COMMUNICATION FAULT

1

COMMUNICATION FAULT

Summary of Contents for Intellibus

Page 1: ...instructions for start up INTELLIBUS PROFIBUS DP FOR INTELLI Intelli 2801 A1150 ...

Page 2: ...ring RedCom with redundancy extensions that can be used if the PLC can support the same extensions According to the fieldbus version required an INTELLIBUS single or redundant line may equip the actuator Control box with inside Profibus DP interface could be supplied to connect other equipment Please make sure to get and read the INTELLI instructions for start up ref NR1151 prior going further wit...

Page 3: ... cross Redundant channel No data exchange empty square Channel 1 is primary and on data exchange rotating triangle Channel 2 is backup and on data exchange alternative up and down triangle Channel 1 Intellibus module fault blinking cross Channel 2 is primary and on data exchange rotating triangle 3 2 Cabletype Use exclusively special PROFIBUS cable conforms to the EN50170 2 standard and of type A ...

Page 4: ...s on No ramifications 3 6 Emergencysupply The actuator INTELLI is normally supplied by the mains but in case of loss of power supply an emergency supply could be used to continue to communicate through the fieldbus This emergency supply needs 24V DC 4W 3 7 ProfibusDParchitecture Single line The Profibus cable coming from the PLC is connected to the first actuator then the Profibus cable links this...

Page 5: ...ommunication The cyclic communication is mainly use for the Process Data are read and written in a well defined timing The useful data are selected in the list below and transmitted in a cyclic way The selection of only a few data also increases the communication speed The acyclic communication is mainly use for maintenance The data are collected only on request that avoid to reduce the cyclic com...

Page 6: ... between proportional and ON OFF control assign an auxiliary command to the function AUTO ON OFF then select the control mode required from the control room see above Address 1 Address 4 Relay output option The relays could be used to have an output indication wired as a non fieldbus actuator or to drive outside devices through Profibus These optional relays could be configured in Intelli menu for...

Page 7: ...g closing direction of rotation discrepant BATTERY LOW OR IS NOT PRESENT In case of battery option the battery should be replaced because of too low voltage or the battery is missing Address 3 Running torque in RUNNING TORQUE Indication of the instantaneous torque 100 is the maximum actuator rated torque Address 4 Actuator position feedback ACTUATOR POSITION FEEDBACK 0 closed 100 open Bit n Value ...

Page 8: ... Bit n Value Description Bit 0 0 NO INDICATION 1 1 INDICATION 1 IS ACTIVE OPTION Bit 1 0 NO INDICATION 2 1 INDICATION 2 IS ACTIVE OPTION Bit 2 0 NO INDICATION 3 1 INDICATION 3 IS ACTIVE OPTION Bit 3 0 NO INDICATION 4 1 INDICATION 4 IS ACTIVE OPTION Bit 4 0 NO INDICATION 5 1 INDICATION 5 IS ACTIVE ESD INPUT BY DEFAULT Bit 5 0 NO VALVE JAMMED ALARM 1 VALVE JAMMED Bit 6 0 NO AUXILIARY 24V FAULT ALARM...

Page 9: ...ures since actuator manufacturing Address 18 to 21 Running time TOTAL RUNNING TIME To obtain the accumulated figures since actuator manufacturing Unit is 1 10 sec Address 22 to 25 Partial number of starts PARTIAL NUMBER OF STARTS Number of starts since the last reset Address 26 to 29 Partial running time PARTIAL RUNNING TIME Total running time since the last reset Unit is 1 10 sec Address 30 and 3...

Page 10: ...er line AvailabledatathroughPROFIBUSacycliccommunication Data is organised in slot and index Slot 0 Indexes 0 to 61 are listed below Index Data Description Byte Read write 0 Set up for auxiliary command 1 0 not used 1 local 0 remote 1 2 local remote 0 remote 1 3 local command inhibit 1 4 open inhibit 1 5 close inhibit 1 6 ON OFF 0 AUTO 1 7 fieldbus emergency closing 1 8 fieldbus emergency opening ...

Page 11: ...torque curve Torque in Data 1 closed position Data 2 1 open Data 101 100 open 101 read only Index Data Description Byte Read write 39 Closing torque curve Torque in Data 1 closed position Data 2 1 open Data 101 100 open 101 read only 40 Profibus slave address 1 125 1 read only 41 Indication address 0 Replicate the data of the cyclic register 1 read only 42 Indication address 1 Replicate the data o...

Page 12: ... 4 39 80 726 MOROCCO AQUATEL sarl aquatel wanadoo net ma CASABLANCA Tel 212 22 66 55 71 NETHERLANDS BERNARD CONTROLS BENELUX NV hans nobels bernardcontrols com AN ZWAAG Tel 31 0 229 298083 NEW ZEALAND MRCTransmark NZ LTD bill sunley mrctransmark com Auckland Tel 64 9 276 4149 NORWAY KSB LINDFLATEN AS firmapost lindflaten no LYSAKER Tel 476 71 29 900 POLAND MARCO matzanke pol pl WARSAW Tel 48 22 86...

Reviews: