II. MOUNTING INSTRUCTIONS (General)

INDOOR MOUNTING ONLY

 - 

The Architectural Elite Air Curtain is designed to be an effective 

barrier against cold drafts in the winter, hot air in the summer,

flying insects, and airborne contaminants.

To achieve optimum protection, the air curtain should be 

mounted on the inside of the building, flush to the wall and 

as close to the top of the door opening as possible.  To ensure 

peak performance, keep the air stream free of obstructions. 

The air curtain will not perform properly if negative air 

pressure exists in the building.  Under these conditions, 

a means for makeup air to the building must be provided 

so that the air pressure on both sides of the opening is in 

balance.

Before mounting the air curtain, check the supporting structure 

to verify that it has sufficient load-carrying capacity to support 

the weight of the air curtain(s). The mounting hardware 

(supplied by others) should be capable of supporting a 

minimum of three (3) times the weight of the air curtain. 

See Table 1.

IMPORTANT:

 A minimum of 4” is required above the top rear

corner  of the air curtain for the installation and removal of the 

inlet screen, and to ensure proper airflow.

A. 

When determining the mounting location for the air 

curtain(s), make sure that nothing interferes with the 

curtain of air developed when the discharge vanes are 

directed from 0° to 20° toward the door opening.  If the 

air stream strikes any obstruction (the top edge of the 

doorway, a door opening device, etc.), the effectiveness 

of the air curtain will be greatly reduced. 

See Figure 2. 

B. 

For optimum performance, the bottom of the air curtain 

(discharge nozzle) should be no more than 1” above the 

top of the door opening with the air curtain(s) mounted 

flush to the wall. If the air curtain must be mounted 

higher, it must be spaced out from the  wall 3/8” for 

every inch the air curtain is above the door opening. 

See 

Figure 3.

 For optimum protection, any void between the 

air curtain and the wall should be sealed along the full 

length of the air curtain.  

C. 

Do not block (obstruct) the air intake screen. Insufficient 

airflow can cause the unit to overheat.

D. 

The air curtain(s) shall:

1. 

Have a minimum clearance of at least 4”  from  

 

 

the sides and 4" from the top.

2. 

Have a minimum clearance of at least 6’  between   

 

the bottom of the air curtain and the floor.  

3. 

Be installed Indoors Only. 

E.     Proceed to either 

Section III - WALL MOUNTING or 

Section IV - SUSPENDED MOUNTING 

Figure 2 - General Mounting

 

 

Figure 3 - Wall Mounting Location

TABLE 1 - Weight Chart

20˚

AIR

Discharge 
Nozzle

4" minimum

side & top 

clearance from 

combustible 

material

A

IR

 

A

IR

 

INTERIOR

EXTERIOR

6' minimum

MODEL

Net Weight

MODEL

Net Weight

AE10 

Ambient

AE10 

Electric

AE10  

Hot 

Water

AE08 

Ambient

AE08 

Electric

AE08 Hot 

Water

AE10-E-1036

100

104

125

AE08-E-1036

52

57

72

AE10-E-1042

112

116

140

AE08-E-1042

59

64

82

AE10-E-1048

125

129

156

AE08-E-1048

66

71

91

AE10-E-2060

168

176

205

AE08-E-1060

81

86

111

AE10-E-2072

193

201

239

AE08-E-1072

95

100

133

AE10-E-2084

218

226

270

AE08-E-2084

117

127

160

AE10-E-2096

244

252

302

AE08-E-2096

132

142

180

AE10-E-3096

262

274

320

AE08-E-2108

146

156

199

AE10-E-3108

287

299

351

AE08-E-2120

157

167

214

AE10-E-3120

306

318

374

AE10-E-3132

337

349

416

AE10-E-3144

362

374

447

AE10-E-4144

380

396

465

Summary of Contents for AE08

Page 1: ...LD CONNECTIONS 6 VII OPERATING INSTRUCTIONS 7 INTELLISWITCH QUICK START OPERATION 10 FAQ s FREQUENTLY ASKED QUESTIONS 12 VIII MAINTENANCE AND CLEANING 8 IX SERVICE 8 X TROUBLESHOOTING 14 XI APPENDIX A SERIAL NETWORK CONNECTION PREVIOUSLY MASTER SLAVE CONNECTION 15 B WALL MOUNTED TOUCHSCREEN 15 XII WARRANTY 16 Installation Maintenance Instructions II 260D May 2020 Copyright 2020 Berner Internationa...

Page 2: ... s in accordance with all applicable national and local codes having jurisdiction including fire rated construction See page 6 ELECTRICAL CONNECTIONS NEC Code ANSI NFPA No 70 E When cutting or drilling into wall or ceiling do not damage electrical wiring and other hidden utilities F To reduce the risk of fire do not store or use gasoline or other flammable vapors and liquids in the vicinity of the...

Page 3: ...nd then it will drop down If the unit must be mounted higher than 1 above the opening it must be spaced out from the wall 3 8 for every inch the unit is above the door opening 2 LOWER LIP GAP NEEDED TO MOUNT UNIT FLUSH WITH TOP OF OPENING MOUNTING SCREWS WALL HANGER MOUNTING SCREWS SPACER SEAL ALONG LENGTH SCREWS Longer units use more than two wall hangers Position outer wall hangers no more than ...

Page 4: ...greatly reduced See Figure 2 B For optimum performance the bottom of the air curtain discharge nozzle should be no more than 1 above the top of the door opening with the air curtain s mounted flush to the wall If the air curtain must be mounted higher it must be spaced out from the wall 3 8 for every inch the air curtain is above the door opening See Figure 3 For optimum protection any void betwee...

Page 5: ...nger 3 Proceed to Section V ELECTRICAL CONNECTIONS III WALL MOUNTING Figure 4 Wall Mounting Preparation Figure 5 Wall Mounting Installation IV SUSPENDED MOUNTING NOTE if the unit was ordered with a decorative rear cover the air curtain will arrive with the cover already installed and the wall mounting hangers mounting catch and hook will not be included in the shipment Contact Berner if they are r...

Page 6: ... temperature sensor located internally to measure the incoming return air stream D Remove the wiring compartment cover E Connect all supply and control circuit wires according to the wiring diagram provided NOTE For Electric and Hot Water heated air curtains provided with an optional remote thermostat mount and wire the thermostat according to thermostat instructions and wiring diagram For Serial ...

Page 7: ...mming Guide go to www Berner com Intelliswitch 2 Unheated units will have the fans activated by a door switch or sensor The unit speed can be selected from the Intelliswitch display 3 Heated units will have fans activated by a door switch or sensor but may also be activated by the thermostat in Comfort Plus Mode The unit speed can be selected from the Intelliswitch display 4 To operate using the B...

Page 8: ... attach the screen Vacuum and or wash with dish soap and water 3 Internal open the bottom access panel by removing the Phillips head screws on the top front of the unit Vacuum and scrape if necessary to remove the build up of dirt and debris The motor s are permanently lubricated and require no additional lubrication 4 Re install the cover and intake screen See Figure 10 5 Switchthepoweronaftercle...

Page 9: ...motor being serviced Remove the 2 8 hex screws from each end of each assembly that attaches the end bracket to the cabinet endplate 6 Remove the 2 12 hex head screws that secure the lower module to the transverse 7 Remove the transverse 8 If the module has electric heaters mark and disconnect the wires Remove the heaters by disconnecting their mounting brackets from the fan housings Take care to n...

Page 10: ...Temp Set Sets the temperature the air curtain will maintain heated units only Start Time Programs the time of day the air curtain becomes active Stop Time Programs the time of day the air curtain stops running Set Time Day Sets the clock time and day used by programming Locked Unit will run as programmed but settings cannot be changed QUICKSTART INSTRUCTIONS For your Berner Air Curtain with Intell...

Page 11: ...ay expires Door opens The air curtain activates immediately when mode is selected Door shuts The air curtain continues to run Door opens The air curtain is off Door shuts The air curtain is off OFF Standard Mode of Operation Options STEP THREE Once the Mode of Operation is selected press the button For heated units only STEP ONE To Start Press the down arrow button once NOTE To change from Mode to...

Page 12: ...tched on accidentally When the service disconnecting means cannot be locked securely fasten a prominent warning device such as a tag to the service panel Even though every Architectural Elite is individually tested at the factory before shipment on occasion improper functionality may be experienced Here is a list of common questions Q Why won t the Intelliswitch light up A There may not be power t...

Page 13: ...ot tied together There is no danger of getting shocked because the signal is 5 volt DC Be sure not to touch the orange wires to anything metal or grounded The heat should shut off when the wires are separated For more complex troubleshooting of either thermal cutouts or heater relays please consult a quali fied electrician or consult the factory Q Why didn t the Intelliswitch save the changes I ma...

Page 14: ...ld reset automatically after cool down if not replace motor Replace switch MOTOR RUNNING FANS ARE NOT ROTATING MINIMUM AIR ELECTRICAL CONTROLS NOT FUNCTIONING WHEN DOOR IS OPEN SYMPTOMS REMEDY CAUSE Broken or damaged flexible hub Shaft rotating inside fan Selector switch is in off position Door limit switch not operating Air directional discharge vanes mis adjusted Inadequate intake clearance Blow...

Page 15: ...e or display of a unit on the network All program settings are included in the installation instructions shipped with the air curtain 5 Models AE08 E and AE10 E air curtains include a wireless controller that works with the Berner App When connected to the local Wi Fi network they can be programmed from a smart phone using the Berner AIR App Serial Network Connection Settings When units with the I...

Page 16: ...nse or liability for repairs made outside its factory without proper written consent from its service manager nor for any transportation charges on apparatus returned to the factory without written authorization by The Company Nothing in the above warranty provisions however shall impose any liability or obligation of any type nature or description upon Berner International if Berner has not recei...