II. MOUNTING INSTRUCTIONS (General)

INDOOR MOUNTING ONLY

 - 

The Architectural High Performance 10 Air Curtain is designed 

to be an effective barrier against cold drafts in the winter 

and hot air in the summer, flying insects and airborne 

contaminants.  

To achieve optimum protection, the air curtain should be 

mounted on the inside of the building, flush to the wall and 

as close to the top of the door opening as possible.  To ensure 

peak performance, keep the air stream free of obstructions. 

The air curtain will not perform properly if negative air 

pressure exists in the building.  Under these conditions, 

a means for makeup air to the building must be provided 

so that the air pressure on both sides of the opening is in 

balance.

Before mounting the air curtain, check the supporting structure 

to verify that it has sufficient load-carrying capacity to support 

the weight of the air curtain(s). The mounting hardware 

(supplied by others) should be capable of supporting a 

minimum of three (3) times the weight of the air curtain. 

See Table 1.

IMPORTANT:

 A minimum of 1” is required above the top of the 

air curtain for the installation and removal of the inlet 

screen. 

A. 

When determining the mounting location for the air 

curtain(s), make sure that nothing interferes with the 

curtain of air developed when the discharge vanes are 

directed from 0° to 20° toward the door opening.  If the 

air stream strikes any obstruction (the top edge of the 

doorway, a door opening device, etc.), the effectiveness 

of the air curtain will be greatly reduced. 

See Figure 2. 

B. 

For optimum performance, the bottom of the air curtain 

(discharge nozzle) should be no more than 1” above the 

top of the door opening with the air curtain(s) mounted 

flush to the wall. If the air curtain must be mounted 

higher, it must be spaced out from the  wall 3/8” for 

every inch the air curtain is above the door opening. 

See 

Figure 3.

 For optimum protection, any void between the 

air curtain and the wall should be sealed along the full 

length of the air curtain.  

C. 

Do not block (obstruct) the air intake grill. Insufficient 

airflow can cause the unit to overheat.

D. 

Electric heated air curtain(s) shall:

1. 

Have a minimum clearance of at least 4”  from  

 

 

the sides and 8" from the top for electric heated    

 units.

2. 

Have a minimum clearance of at least 6’  between   

 

the bottom of the air curtain and the floor.  

3. 

Be installed Indoors Only. 

E.     Proceed to either 

Section III - WALL MOUNTING or 

Section IV - SUSPENDED MOUNTING 

Figure 2

 

 

Figure 3

1"

2"

Lower Lip

3/8"

Mounting

Screws

Mounting

Plate

Mounting

Screws

FLUSH WALL 

MOUNT

EXTENDED 

WALL MOUNT

Spacer

Spacer

Seal

TABLE 1 - Weight Chart

WEIGHT IN POUNDS

Model

Unheated Electric Steam/Hot Water

AHD10-1036

65

71

98

AHD10-1042

68

74

104

AHD10-1048

70

76

109

AHD10-2048

95

107

135

AHD10-2060

125

137

171

AHD10-2072

130

142

182

AHD10-2084

140

152

198

AHD10-2096

145

157

209

AHD10-3096

165

183

229

AHD10-3108

170

188

241

AHD10-3120

175

193

249

6' minimum

20˚

8" minimum*

AIR

Discharge 
Nozzle

4" minimum

side 

clearance 

from

 

combustible

 

material*

A

IR

 

A

IR

 

*Electrically Heated Units Only

INTERIOR

EXTERIOR

Summary of Contents for AHD10

Page 1: ...ING INSTRUCTIONS 7 INTELLISWITCH QUICK START OPERATION 9 FAQ s FREQUENTLY ASKED QUESTIONS 11 VIII MAINTENANCE AND CLEANING 8 IX SERVICE 8 X TROUBLESHOOTING 13 XI APPENDIX A SERIAL NETWORK CONNECTION P...

Page 2: ...aving jurisdiction including fire rated construction See page 6 ELECTRICAL CONNECTIONS NEC Code ANSI NFPA No 70 E When cutting or drilling into wall or ceiling do not damage electrical wiring and othe...

Page 3: ...ace add locking screws 2 Locking Screws One In Each Corner Mounting Plate 45 Lip and Rubber Vibration Gasket Discharge Nozzle Before hanging check to see what the clearance is above the door 6 minimum...

Page 4: ...rway a door opening device etc the effectiveness of the air curtain will be greatly reduced See Figure 2 B For optimum performance the bottom of the air curtain discharge nozzle should be no more than...

Page 5: ...2 Lower the unit into place allowing it to rest on the lower lip of the mounting plate 3 After the unit is securely attached to the mounting plate re install the two 2 locking screws at the bottom cor...

Page 6: ...e temperature is to be measured the sensor may be left on the endplate or positioned elsewhere Do not put any clamps on the rubber coated tip D Remove the junction box cover E Connect all supply and c...

Page 7: ...ts will have the fans activated by a door switch or sensor The unit speed can be selected from the Intelliswitch display 3 Heated units will have fans activated by a door switch or sensor but may also...

Page 8: ...ps head screws on the bottom of the unit Vacuum and scrape if necessary to remove the build up of dirt and debris The motor s are permanently lubricated and require no additional lubrication Re instal...

Page 9: ...to run after the door closes Start Time Programmable time of day air curtain becomes active Stop Time Programmable time of day air curtain stops running T Stat Mode Set only heat or heat fan Set Time...

Page 10: ...ir curtain turns off Door opens The air curtain activates Door shuts The air curtain continues to run Door opens The air curtain is off Door shuts The air curtain is off OFF 5 Standard Mode of Operati...

Page 11: ...e panel and lock the service disconnecting means to prevent power from being switched on accidentally When the service disconnecting means cannot be locked securely fasten a prominent warning device s...

Page 12: ...curtain is heated make sure that the thermostat isn t wired to the door switch leads Door switch leads are blue and labeled 9 10 Q How can I check the door switch to be sure it s working A The Intelli...

Page 13: ...FANS ARE NOT ROTATING MINIMUM AIR ELECTRICAL CONTROLS NOT FUNCTIONING WHEN DOOR IS OPEN SYMPTOMS REMEDY CAUSE Broken or damaged flexible hub Shaft rotating inside fan Selector switch is in off positio...

Page 14: ...operated in a network there are three options available under the Programming Menu that manage how they interact with each other Door Switch door Thermostat temp Stand By Stby Each option can be set t...

Page 15: ...PURE mode operation When the door opens The air curtain and if applicable the heater s activate and run at set speed When the door closes for heated models The PURE mode allows for the air curtain to...

Page 16: ...iability for repairs made outside its factory without proper written consent from its service manager nor for any transportation charges on apparatus returned to the factory without written authorizat...

Reviews: