Installation Instructions
BPL-HAB20 Installation continued:
Mounting heater at 30° from horizon.
The figure below shows the minimum mounting distances to achieve the clearance to combustibles.
Note: When assembling hanging brackets the maximum angle the heater can be
at is 30° from horizon.
8.85
10.00
9.00
13.75
30°
30°
Minimum Ceiling Mount Distance
Minimum Wall Mount Distance
LEFT side view
Cut unistrust to 13.75"
to achieve the minimum
clearances to combustibles
for this model
Use these bolt
holes for positioning
at this angle.
Use these bolt
holes for positioning
at this angle.
Cut unistrust to 10.00"
to achieve the minimum
clearances to combustibles
for this model
Use these bolt
holes for positioning
at this angle.
15°
30°
15°
30°
15°
30°
RIGHT side view
LEFT side view
Note:
Other clearances must be maintained
as per clearance to combustibles table.
LEFT side view
Note:
Other clearances must be maintained
as per clearance to combustibles table.
LEFT side view
15°
30°
RIGHT side view
March, 2013
BERNER PATIO+ Luminous