background image

-3-

E.  The air door is weatherproof. Therefore, no special covering 

is required when outdoor mounting unheated, steam, or hot 

water units.  

 

NOTE:  Electric heated units are to be installed indoors 

only.

F. 

IMPORTANT:

 A minimum of 4” (8” preferred) clearance 

is recommended above the top of the air door for the 

installation and removal of the screen or to gain access to 

junction boxes.

G.  When determining the mounting location for the unit(s), 

make sure that nothing interferes with the curtain of air 

developed when the discharge vanes are directed from 0º 

to 20º toward the door opening. If the air stream strikes any 

obstruction (the top edge of the doorway, a door opening 

device, etc.), the effectiveness of the unit will be greatly 

reduced.  

See Drawing 1.

H.  For optimum performance, the bottom of the unit 

(discharge nozzle) should be no more than 1” above the top 

of the door opening with the unit mounted flush to the wall. 

If the unit must be mounted higher, it must be 

spaced out

 

from the wall 

³/₈” for every inch

 the unit is above the door 

opening. 

See Drawing 2.

I. 

 Electric heated units shall:

  1.  Have a minimum clearance of at least 1” between the

      sides and top of the unit and any combustible material.

  2.  Have a minimum clearance of at least 6’ between the

      bottom of the unit and the floor.

  3.  Be installed indoors only.

J. 

Proceed to one of the following sections, depending 

  on application and door type:

  Section III: Wall Mounting
  Section IV: Suspended Mounting
  Section V: Vertical Mounting
  Section VI: Tandem Mounting Brackets for Vertical Mounting

DRAWING 1 

DRAWING 2

FIGURE 1 - Wall Mounting

FIGURE 2 - Wall Mounting Bracket

III. WALL MOUNTING

A.  Wall mounting works well with standard hinged doors or   

  sliding doors.

B.  The IDC12/IDC14 Series end plates are equipped with ½”   

holes  for wall mounting. The unit may be attached to the wall  

    using, at minimum, ³/8” bolts through the holes on the back  

  of the end plate. 

See Figure 1

.  Or, the unit may be attached  

  using an optional wall mounting bracket or a combination  

  of extension and wall mounting brackets (available from   

  Berner) attached to the holes on the top of the end plate   

  and the wall.  

See Figure 2

.

C. 

Electrical Connections - 

Proceed to 

Section VII. 

EXTERIOR

INTERIOR

Summary of Contents for IDC12 Series

Page 1: ...n in use To avoid burns do not let bare skin touch hot surfaces Keep combustible materials such as furniture pillows bedding papers clothes etc and curtains at least 1 inch from the top back front sides and at least 6 feet from the discharge of the air curtain H Extreme caution is necessary when any air curtain is used by or near children or invalids and whenever the heater is left operating unatt...

Page 2: ... airflow through this void C The air door will not perform properly if negative air pressure exists in the building Under these conditions a means for makeup air to the building must be provided so that the air pressure on both sides of the opening is in balance D Before mounting the air door check the supporting structure to verify that it has sufficient load carrying capacity to support the weig...

Page 3: ...inch the unit is above the door opening See Drawing 2 I Electric heated units shall 1 Have a minimum clearance of at least 1 between the sides and top of the unit and any combustible material 2 Have a minimum clearance of at least 6 between the bottom of the unit and the floor 3 Be installed indoors only J Proceed to one of the following sections depending on application and door type Section III ...

Page 4: ...lates are equipped with holes for suspended mounting The unit may be suspended using a minimum 8 suspension rod Figure 3 or using 8 suspension rods and extension brackets available from Berner See Figure 4 C Electrical Connections Proceed to Section VII V VERTICAL MOUNTING A Vertical mounting works well when the opening is taller than it is wide or when the door type prevents a typical over door m...

Page 5: ... install the Junction Box cover NOTE For electric heated units provided with optional remote thermostat Mount and wire the thermostat according to instructions and wiring diagram VIII MECHANICAL CONNECTIONS A ELECTRIC HEATED MODELS The heater circuit may be controlled by a remote thermostat or manually through the switch located on the discharge side of the unit Overheating protection is provided ...

Page 6: ...r is being directed to both the inside and the outside See Figure 11 The split location is indicated where the handkerchief is vertical with minimal or no fluttering 3 The split location should be approximately 3 outside the doorway If necessary adjust the discharge nozzle vanes by de energizing the unit loosening the nozzle vane locking screws and adjusting vanes X MAINTENANCE AND CLEANING CAUTIO...

Page 7: ... Allen wrench The set screw can be accessed up through the fan discharge or through the small hole on the back of the blower housing 8 Next remove the blower housings by removing the 4 self drilling screws from the back of the fan housing The fan housing and fan impellers may now be slid off of the motor shaft 9 To remove the Motor remove the motor clips from the motors and disconnect the motor gr...

Page 8: ...y expense or liability for repairs made outside its factory without proper written consent from its service manager nor for any transportation charges on apparatus returned to the factory without written authorization by The Company Nothing in the above warranty provisions however shall impose any liability or obligation of any type nature or description upon Berner International if Berner has not...

Reviews: