background image

2

|

2

3 IMPLEMENTATION

3.1 TESTING AND REPORTING PROCEDURE

Basic testing and reporting procedure is set out in BESA publication SFG 20. This section is to inform

members of minimum requirements for testing and reporting. Additional procedures maybe required

by the client. All contractors need to have su

ffi

cient training to carry out mechanical work. Please 

contact the BESA training department on 

training.courses@theBESA.com

for support in the form of

a seminar, presentation or training course. Testing should include but is not limited to the following

steps.

An inventory of all dampers to be tested.

All Fire/Smoke dampers will be manually released to ensure the integrity of the spring loaded 
shutter.

The Fusible link should be inspected for any deformity or damage.

The Fire/Smoke Damper will be cleaned and lubricated within the closed position.

The Fire/Smoke Damper shall then be opened and re-set.

Any severe corrosion found shall be reported to the client.

Reports should include but are not limited to the following items: 

Test results with client information including position within the building/system, date, and 
name of operative shall be recorded and any comments noted if further action is required.

Asset register to include damper location and ID number.

Inspection results including details of failed damper operation.

If drawings are provided, update and annotate details. 

Digital photographic evidence of damper condition prior to and after testing procedures un
less otherwise speci

fi

ed by client.

Explanation of failed operation and recommended corrective or remedial action.

4 SCOPE AND ACKNOWLEDGEMENTS

TB/001 Fire and Smoke Damper Maintenance is designed to be used in conjunction with BESA publications which are
regularly reviewed by the BESA Technical Department to ensure they re

fl

ect current British, European and industry

standards. Please refer to BS9999 and HTM 03-01 for additional information. The BESA would like to thank members 

of the Vent Hygiene Group for supplying content. All content correct at time of publishing.

Note

: this document is based on knowledge available at the time of publication and is meant for general purposes, not

for reliance on in relation to speci

fi

c technical or legal issues, in which case you should always seek independent advice.

No responsibility of any kind for any injury, death, loss, damage or delay however caused, resulting from the use of the

advice and recommendations contained herein, is accepted by the authors or others involved in its publication 

(including the Building  Engineering Services Association).  19/01/2016

TECHNICAL

BULLETIN

TB/001

FIRE AND SMOKE DAMPER MAINTENANCE

Reviews: