Installation Instructions for 45HM IDH Max® 1300 Mortise Locks
BEST ACCESS SYSTEMS
a Division of Stanley Security Solutions, Inc.
11
Installation Instructions for 45HM IDH Max® 1300 Mortise Locks
Installing the trim
16
Set the control electronics board DIP
switches
Each IDH Max unit must be addressable (able to be identi-
fied automatically by the access control system) with a
unique address that matches its Lenel or B.A.S.I.S.® reader
address set up in the management software. See the
Sys-
tem Administration User Guide
for more information on
reader addressing.
1 On the inside control electronics board use the first
five switches to set the reader address in binary code.
Switch one is the least significant digit. See the table
on the next page.
2 Use the table below to set both switches 6 and 7 to the
baud rate at which the locks will communicate with
the intelligent controller.
3
For the last IDH Max Lock in the daisy-chain only
, set
switch 8 to ON. Otherwise, set switch 8 to OFF.
Baud rate
Switch 6
Switch 7
2,400
All off
9,600
ON
19,200
ON
38,400
ON
ON