25
Rated Capacity
3 KVA/
2100 W
6 KVA/
4200 W
9 KVA/
6300 W
12 KVA/
8400 W
15 KVA/
10.5 KW
18 KVA/
12.6 KW
Recommended
Input Service
(Amp)
Typical Input
Voltage and Current
(VAC — Amp AC)
25
200*
18
208
17
220
16
230
15
240
15
50
200*
36
208
34
220
32
230
31
240
30
70
200*
54
208
51
220
49
230
47
240
45
100
200*
71
208
69
220
65
230
62
240
59
125
200*
89
208
86
220
81
230
78
240
74
150
200*
107
208
103
220
97
230
93
240
89
Output Voltage and
Max. Current
(VAC — Amp AC)
100/200* 30/15
208
14.4
220
13.6
110/220
27/14
230
13
240
12.5
120/240 25/12.5
100/200* 60/30
208
28.8
220
27.2
110/220
54/28
230
26
240
25
120/240
50/25
100/200* 90/45
208
43.2
220
40.8
110/220
81/42
230
39
240
37.5
120/240 75/37.5
100/200*120/60
208
57.6
220
54.4
110/220 108/56
230
52
240
50
120/240 100/50
100/200*150/75
208
72
220
68
110/220 135/70
230
65
240
62.5
120/240 125/62
100/200*180/90
208
86.4
220
81.6
110/220 162/84
230
78
240
12.5
120/240 150/75
Heat Dissipation
(in Double Conv.)
Watts (kBtu/hr)
Efficiency in
Bypass Mode
(Isolated Output)
Efficiency in
Double Conversion
(Isolated Output)
Efficiency in
Double Conversion
285
(0.98)
570
(1.95)
860
(2.93)
1145
(3.90)
1430
(4.88)
1720
(5.85)
> 96%
> 84%
> 88%
Audible Noise
(dBA)
< 53
Agency Listings and Compliance
Safety:
All models comply with UL, cUL, TÜV, CE.
Emissions: All models comply with (Class A) FCC, ICES, CISPR-22, VCCI, C-tick, BCIQ.
Immunity: All models comply with EN 50091-2.
Table 7. Axxium Pro UPS Operating Specifications
* Available only with split-phase power modules.