29
1000 How Do I. . .
The following questions provide a few quick-to-find answers to commonly asked questions. Use this
information after you are completely familiar with Axxium Pro system operation and all other parts of this
manual.
Turn the UPS on?
Make sure all power modules are securely plugged into the rack, and each module handle is latched. Also make
sure the DC disconnect button on the back of the external battery cabinet is closed (pulled out). Turn the
optional external bypass switch to the Line or UPS position. Press the button labeled ON. (If On/Off control is
password-protected, you’ll be requested to enter the User password: 0377.) Confirm the selection by pressing the
button labeled Yes. After a few seconds, the green LED lights to signal the UPS is operating and producing
power.
Turn the UPS off?
Press the button labeled OFF and confirm the selection by pressing the button labeled Yes. (If On/Off control is
password-protected, you’ll first be requested to enter the User password: 0377.) In the event of a control panel
failure, you can turn the unit on or off using a computer connected to the Communication Port. In an emergency
or when the above two methods fail to turn the unit off, remove the front cover bezels, and unlatch and pull the
handles of all power modules out at least one inch (20 mm) to turn off the power control circuitry. If your UPS
has external battery cabinets, press the large, red DC disconnect button on the back of the battery cabinet.
Turn off the alarm beeps?
Press the lower left button. Note the alarm message and refer to the Alarm Messages table to correct the
problem. After the problem has been resolved, press the lower center button to clear the alarm.
View the alarm log?
Go to menu 9 2. Press the enter button to view the most recent alarm. Press the down button to scroll down
through the log to view older alarms.
Install the CheckUPS software?
See the instructions accompanying the CheckUPS software CD-ROM. For the latest software revision, download
it from www.bestpower.com.
Check the battery voltage?
Go to menu 3 5. To view other system status parameters, refer to the Menu Map.
Check the input or output voltage?
Go to menu 3 8 for the input voltage; go to menu 3 10 for the output voltage.
Change the battery low-voltage alarm threshold? (or any other alarm or operating limit?)
This is one of the parameters that requires a trained person, knowing the correct password, to perform. Without
the proper password, you are only able to view operating limits, not change them. These limits should be
changed only by authorized personnel. For information about making this or other password-protected
adjustments, contact Best Power's Worldwide Service or your nearest Best Power office.