26
7F. Changing the Fortress’ Baud Rate
As shipped, your Fortress is set to communicate at a baud rate of 1200. If you want to
use two-way communication, but your computer or terminal cannot communicate with
the Fortress, make sure the computer or terminal is also set to 1200 baud. If you want to
change the Fortress’ baud rate, you must establish two-way communication with the
Fortress; for instructions,
8. About Your Fortress
8A. General Specifications
E
N
G
L
I
S
H
LI 720
LI 1420
Capacity (VA, Watts)
720 VA, 470 Watts
925 VA, 925 Watts
Battery Voltage
48 VDC
48 VDC
Dimensions Height:
Width:
Depth:
9.25 in. (235 mm)
7 in. (180 mm)
17 in. (435 mm)
9.25 in. (235 mm)
7 in. (180 mm)
17 in. (435 mm)
Weight UPS:
LIXRBP-6614:
LIXRUGK-6613:
55 lbs. (25 kgs.)
65 lbs. (29.5 kgs.)
50 lbs. (22.7 kgs.)
60 lbs. (27.2 kgs.)
65 lbs. (29.5 kgs.)
50 lbs. (22.7 kgs.)
Audible Noise
44 dBA from front on line,
48 dBA from other sides on line.
Lightning and
Surge Suppression:
Passes ANSI/IEEE C62.41 Categories A and B2. Zero Surge
Clamping Response Time. 120-volt units are UL 1449 listed.
Surge Voltage
Let Through:
Lets through 0.7% of peak in ANSI/IEEE C62.41 1991
Category A exposure level 3 test.
Noise (RF)
Isolation:
Normal and common mode EMI/RFI suppression. Full-time
advanced multi-stage filter.
Efficiency:
92% on line.
Input Protection:
Fuse: See the label on the back of the UPS for size and type.
describes how to replace the fuse.
Output Protection: Automatic (current and overvoltage).
Output Waveform: Sine-wave, 5% or less THD on inverter; same as line on AC
line.
Output Frequency: 50 or 60 Hz ±0.5 Hz on battery. Frequency on line is the same
as line from 45 to 65 Hz.