background image

9

ENGLISH

Replacement Instructions - 400VA Models

1

Phone Best Power’s Worldwide Service to order a replacement battery pack. It must be the
same type and rating as the original battery. See Battery information in Specifications.

2

If it is necessary, the battery may be replaced while the Patriot Pro II is running with the 
protected equipment attached. Option: You may switch off and unplug the protected load
equipment from the Patriot Pro II. Then, turn off the Patriot Pro II and disconnect the line
cord.

3

On the bottom of the Patriot Pro II, remove the Phillips screw at the end of the battery door 
and slide the door off.

4

Use the flap attached to the battery to lift it out of the unit.

5

Disconnect the battery cables form the old 
battery. Dispose of the old battery properly.

6

Connect the battery cables to the new battery: red 
to positive (+), black to negative (-). Carefully 
install the battery back into the Patriot Pro II.

7

Slide the battery door back into place and secure 
with the Phillips screw removed in step 3.

8

If you followed the option in Step 2:
Reconnect the line cord to the Patriot Pro II unit 
and turn the unit on.  Reconnect the load 
equipment. Switch on the protected load 
equipment one piece at a time.

Red

Black

Summary of Contents for Patriot Pro II 1000 VA

Page 1: ...USER GUIDE Patriot Pro II 400VA 750VA and 1000VA B ...

Page 2: ...English 1 ...

Page 3: ...Patriot Pro II 400VA 750VA and 1000VA User Guide LTM 1325A Copyright 1999 Best Power All rights reserved B ...

Page 4: ...u prefer you can contact Best on the World Wide Web to get more product information Best s toll free Fax on Demand service is also available 24 hours a day to give you access to technical notes and product information Worldwide Service 1 800 356 5737 U S Canada or 1 608 565 2100 Worldwide Service FAX 1 608 565 7642 or 1 608 565 2509 World Wide Web Site http www bestpower com Sales Fax on Demand 1 ...

Page 5: ...tructions 400VA Models 9 Replacement Instructions 750VA and 1000VA Models 10 Communication Port 11 Pinouts 11 Specifications 12 Warranty 13 Best Power Offices 16 Appendix A Adjusting Voltage Settings 17 Trademarks Windows is a registered trademark of Microsoft Corporation All other brand and product names are trademarks or registered trademarks of their respective holders ...

Page 6: ... If stored above 25 Celsius 77 Fahrenheit recharge the batteries more often CAUTION Whenever the unit s On Off is On there may be dangerous voltage present at the unit s outlets This is true because the unit s battery supplies power even if the unit is not plugged into the wall outlet The unit contains dangerous voltages To reduce the risk of electric shock install in a temperature controlled and ...

Page 7: ...ront panel LEDs and an audible alarm keep you aware of the unit s status Use the drawings below to identify features of the unit Front and Side Views of 400 750 and 1000 Models RS 232 RJ11 RJ45 Output Receptacles U E Input U Cord and Plug Input E Receptacle FUSE FUSE 400U 750 1000U 400E 750 1000E Patriot Pro II Controls and Indicators On Standby Button Alarm Program Button Load or Battery Charge s...

Page 8: ...otect and plug it into the outlets on the back of the Patriot Pro II 5 Switch on the protected equipment one at a time If the UPS beeps an alarm when you start your equipment the UPS may be overloaded See the Troubleshooting section The bottom four lights on the front of the UPS show the of the UPS power that your equipment is using See Symbols LEDs and Audible Beeps Section for more information 6...

Page 9: ...nt the unit from switching to battery Buck Automatically decreases high input power to prevent the unit from switching to battery Table 1 Symbols and LEDs AC LINE Green LINE CORRECTION Green BATTERY MODE Yellow OVERLOAD D LED Yellow WARNING D LED Yellow Steady Patriot Pro II is operating on AC line Blinking Patriot Pro II is bucking or boosting input AC line Steady Patriot Pro II is operating on b...

Page 10: ...place the Battery The battery needs to be replaced See Replacing the Batteries To silence an alarm press the ALARM SILENCE button on the front panel The beep will stop but the alarm light will stay on Note Silencing the alarm does not solve the problem that caused it See Tables 2 and 3 If your Patriot Pro II runs on batteries frequently because the input utility line varies often you may want to a...

Page 11: ...w BATTERY LED on green LINE LED off two beeps every 10 seconds Very low battery voltage Plug the unit into a working wall outlet for at least 8 hours to allow the batteries to charge After recharge if the Patiot Pro II will not operate on batteries or Patriot Pro II beeps twice every 10 seconds onbatteries phone Best Power s Worldwide Service Green LINE LED on Yellow WARNING LED on three beeps eve...

Page 12: ...jects could fall into the UPS Never allow any tool to contact both a battery terminal and the UPS cabinet or another battery terminal Do not lay tools or metal parts on top of batteries To ensure continued superior performance from your UPS and to maintain proper charger operation you must replace the UPS batteries with the same number and type of batteries These batteries must be the same type as...

Page 13: ...e bottom of the Patriot Pro II remove the Phillips screw at the end of the battery door and slide the door off 4 Use the flap attached to the battery to lift it out of the unit 5 Disconnect the battery cables form the old battery Dispose of the old battery properly 6 Connect the battery cables to the new battery red to positive black to negative Carefully install the battery back into the Patriot ...

Page 14: ...ribbon cable attached on top of the unit so it is out of your way while replacing the batteries 4 Remove the two screws from the interior panel to gain access to the batteries 5 Disconnect the red and black cables from the used battery pack 6 Use the label attached to the batteries to remove the batteries from the Patriot Pro II 7 Slide the new batteries into the unit Reconnect the cables to the n...

Page 15: ...Common after the UPS switches to battery power Pin 4 Common The signal ground for all signal pins Pin 5 Normally Open Low Battery Alarm Contact A normally open contact that closes pulls to Common during a Low Battery Alarm This tells CheckUPS II and other shutdown software when to start a computer shutdown Pin 6 Plug and Play Sense for Windows 95 Pin 7 Remote Shutdown Shorting this pin to Common f...

Page 16: ...tes 400VA Model Full load 4 5 minutes Half load 17 minutes 750VA Model Full load 4 5 minutes Half load 17 minutes 1000VA Model Full load 4 5 minutes Half load 15 minutes Transfer Time 2 6 ms typical Telephone line surge suppression for U models per Bellcore 1089 1 2 50msec waveform 2kV peak Compliant to UL497A Battery Sealed maintenance free valve regulated UL 924 recognized 400 VA Models One 12 V...

Page 17: ...3 mm 750VA 8 25 x 6 5 x 14 25 in 213 x 163 x 363 mm 1000VA 8 25 x 6 5 x 14 25 in 213 x 163 x 363 mm Weight 400 17 5 lbs 7 5 kg 750 31 lbs 14 kg 1000 35 5 lbs 16 kg Warranty LIMITED TWO YEAR WARRANTY Standard Warranty For All Purchases BEST POWER a division of SPX Corporation hereinafter called BEST POWER warrants that each product sold by BEST POWER is compatible with existing commercially availab...

Page 18: ... not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from state to state You are advised to consult applicable state laws No warranty is made with respect to other products sold by BEST POWER which do not bear the name BEST POWER and no recommendation of such other product shall imply or constitute any warranty with respect to them This warr...

Page 19: ...rounded in accordance with instructions received from BEST POWER and the PURCHASER shall also specify the computer equipment to which the Product sold has been connected and the location of the computer equipment This warranty will not apply to any equipment not specified in the application by the PURCHASER as protected equipment EXCEPT AS EXPRESSLY SET FORTH IN THIS WARRANTY AND BEST POWER S LIMI...

Page 20: ...la Australia Ltd 13 Healey Road Dandenong Victoria 3175 AUSTRALIA Telephone 61 3 9706 5022 FAX 61 3 9794 9150 E mail sola solaaust com au Best Power Technology Limited BEST House Wykeham Industrial Estate Moorside Road Winchester Hampshire SO23 7RX ENGLAND Telephone 44 1962 844414 Toll Free 0800 378444 FAX 44 1962 841846 Best Power Technology Germany GmbH Am Weichselgarten 23 D 91058 Erlangen GERM...

Page 21: ...ervice at 1 800 356 5737 or 1 608 565 2100 Do not change voltage settings when unit is operating on inverter To change the values follow these steps 1 Press the button shown until the LEDs on the front of the Patriot Pro II blink After the LEDs blink three will stay lit and the Patriot Pro II will beep for one second 2 The LEDs that are lit show which voltage settings are selected The LEDs are num...

Page 22: ...atriot Pro II will save the setting that is displayed Continue pressing the button until the proper LEDs are lit 4 Once the correct LEDs are lit continue to hold the button for 10 seconds to save your changes If the Patriot Pro II is running on AC input power the display will change back to the percent of full load The new values will take effect after the display returns to normal mode Press this...

Page 23: ...6 109 128 146 156 1 2 5 90 104 128 146 156 Table 4 Voltage Settings for U Models 400U 750U and 1000U Table 5 Voltage Settings for E Models 400E 750E and 1000E 270 244 230 200 180 3 4 6 284 250 230 210 188 2 4 5 270 244 230 210 188 3 4 5 Default 290 264 240 210 188 1 3 5 284 250 240 210 188 2 3 5 290 264 240 222 200 1 3 4 284 250 240 222 200 2 3 4 To Inverter Input AC is High Buck Nominal Voltage B...

Page 24: ...llation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and the receiver Connect the equipment into an outlet on a ci...