14
SOLA Never Stops Innovating
www.solaaust.com.au
Battery Replacement Instructions
(1000VA and 1500VA only)
1
Phone SOLA Service to order a replacement battery pack. It must be the same type and
rating of the original batteries. See Battery information in Specifications.
2
If it is necessary, the batteries may be replaced while the Sola 620 Rackmount is running,
with the protected equipment attached. Option: You may switch off and unplug the
protected load equipment from the Sola 620 Rackmount. Then, turn off the Sola 620
Rackmount and disconnect the line cord.
3
Use the drawing below to identify the location on the battey pack in the Sola 620
Rackmount.
4
Remove the screws holding the exterior battery access panel (1) to the front panel. Set the
screws and panel aside.
5
Remove the screw holding the interior panel (2) to the battery chamber. Use care to avoid
dropping screw inside the unit. Set the screw and panel aside.
6
Unplug the battery connector from its mating socket.
7
Pull the tray of batteries from the Sola 620 Rackmount. Do not pull batteries out by pulling
on battery terminals or cables. The 1000VA unit has three batteries on its tray; the 1500VA
unit has four batteries.
8
Position the new battery tray and its cables so they will not be pinched by the interior panel
or the battery pack. Slide the battery pack into the unit.
9
Reconnect the cable to the new battery pack.
10
Use the screws removed earlier to
re-install the interior panel to the
battery chamber and the exterior
panel to the front panel.
11
If you followed the option in step 2:
Reconnect the line cord to the Sola
620 Rackmount and turn the unit on.
12
Reconnect the load equipment.
Switch on the protected load
equipment one piece at a time.
1
2