15
SOLA Never Stops Innovating
www.solaaust.com.au
Interface Port
The Sola 620 Rackmount comes equipped with CheckUPS II power management software.
Instructions included with the CheckUPS II CD tell you how to install the software. An interface
cable for the following systems is provided.
SCO UNIX/XENIX
UNIX and Compatible Systems
OS/2
Windows 3.X, 95 and NT
Novell NetWare
SOLA offers interface kits that allow you to connect many other computer systems to the Sola
620 Rackmount interface port. For the following computer systems, or specific information on
SOLA interface kits, call SOLA Service or your local SOLA dealer.
Banyan VINES
IBM RS/6000 AIX
IBM AS/400 special
Lantastic v4.0
LAN Manager/Server v2.0
Interface Port Pinouts
Pin 1
RS232 Receive Data: Receives incoming RS232 communication data.
Pin 2
RS232 Transmit Data: Sends outgoing RS232 communication data.
Pin 3
Normally Open On-Battery Contact: A normally open contact that closes 15 seconds
(pulls to Common) after the UPS switches to battery power.
Pin 4
Common: The signal ground for all signal pins.
Pin 5
Normally Open Low-Battery-Alarm Contact: A normally open contact that closes
(pulls to Common) during a Low Battery Alarm. This tells CheckUPS II and other
shutdown software when to start a computer shutdown.
Pin 6
Reserved.
Pin 7
Remote Shutdown: Shorting this pin to common for at least 5 seconds, while the UPS is
operating on battery, shuts the UPS off after 120 seconds. NOTE: The shutdown
sequence must continue even if AC line returns during the 120 second countdown.
Pin 8
Normally Closed On-Battery Contact: A normally closed contact that opens
15 seconds (releases from Common) after the UPS switches to battery power.
Pin 9
Normally open bypass switch status contact. A normally open contact that closes
(pulls to common) whenever the UPS is in an Internal Bypass mode or is being
bypassed through the use of a bypass switch.
Contacts consist of open collector circuits capable of switching up to +30 VDC, 6 mA resistive
load. The internal pull-up voltage on pins 3, 5, 8, and 9 is +12 VDC.
An Emergency Power Off (EPO) function is available through the interface port. Contact SOLA
for specific technical details.