Installation Instructions for IDH Max 1300 Mortise Locks
BEST ACCESS SYSTEMS
A Division of Stanley Security Solutions, Inc
3
Installation Instructions for IDH Max 1300 Mortise Locks
Components checklist
Special tools checklist
❑
Field wiring for power connections between the lock
and power supply or the lock and access control panel.
If you’re powering the lock(s) through the access
control panel, calculate the total length of the power
wire run by summing:
■
The distance from the power supply to the access con-
trol panel.
■
The distance from the access control panel to the first
door.
■
If powering more than one door daisy-chained to the
same power supply, add the total distance of the
power runs between the doors.
If you’re powering the lock(s) using a separate power
supply, calculate the total length of the power wire run
by summing:
■
The distance from the power supply to the first door.
■
If powering more than one door daisy-chained to the
same power supply, add the total distance of the
power runs between the doors.
Refer to the table below to determine the minimum
wire gauge based on the number of doors sharing the
power supply and the total length of the wire run.
❑
Field wiring for RS-485 communication connections
between the lock and access control panel (4000 feet
maximum):
Category 5, shielded twisted pair; 24 AWG min.
Maximum wire length based on
no. of doors daisy-chained to power
supply
Minimum
wire gauge
1 door
2 doors
3 doors
4 doors
250 feet
125 feet
75 feet
60 feet
18 AWG
400 feet
200 feet
130 feet
100 feet
16 AWG
600 feet
300 feet
185 feet
150 feet
14 AWG
Use the following checklist to make sure that you have the
special tools necessary to install the components pro-
vided with your 34HM–35HM IDH Max Mortise Lock.
❑
Three (3) to four (4) foot, 3/8
″
drill bit
❑
T15 TORX® bit driver
‡
‡ TORX is a registered trademark of the Camcar
Division of Textron.