Quick-Start Guide
E2K-210-10-17 Rev. 2
October 2017
6
Setting Position Limits for Manual Operation
Setting Position Limits for Manual Operation
Setting Position Limits for
Manual
Operation
STEP 1:
CLOSED Valve Position
2
3
4
YES
LOCAL
1
STOP
5
Depress
declutch,
rotate
handwheel
until...
declutch is fully
engaged.
Release
declutch,
rotate toward
open for 1 turn.
Turn the selector knob to the
LOCAL
position. At the
“CLOSE VALVE THEN SELECT STOP”
prompt, depress the
declutch lever
while rotating the
handwheel
until the clutch is fully engaged. Release the lever.
When the valve is fully closed, move the valve in the open direction for one handwheel turn to allow for
coasting of the motor. Return the selector knob to the
STOP
position. At the
“ACCEPT CLOSE LIMIT”
prompt,
select
“YES.”
Advance to the
“SAVE CHANGES?”
prompt and answer
YES
to save the changes.