Fire damper BSK9

EI90

Installation

BSK9 is installed in fire cell separating walls or floors, 
according to the adjoining installation instructions. Should 
not be installed outdoors, in damp or high humidity areas.

Actuator

BSK9 is always supplied with an electric safety actuator 
with spring return complete with thermal sensor equipped 
with push button for local manual operating test. The sen-
sor breaks the power supply to the actuator device if the 
temperature exceeds 72 °C inside or outside the damper. 
24 V actuators are always used with the FENIX monitoring 
system, MRB3 and MRB. The damper can also be supplied 
with 230 V electric actuator. The damper is always supplied 
with a safety actuator.

Activation

The Boverket Building Regulations state a requirement  
for smoke detectors verified in accordance with  
SS-EN 54-7 for activation of dampers. The obligatory 
 thermal sensor closes the damper at 72 °C in accordance 
with ISO 10294-4.

Control and monitoring

Dampers for protection against the spread of fire and com-
bustion gases shall be closed via inputs from a smoke de-
tector. Smoke detectors are mounted in ventilation ducts 
or monitored spaces. Fire dampers, smoke detectors and 
ventilation units are connected to the FENIX, MRB3 or 
MRB control unit for a complete ventilation fire protection. 
FENIX, MRB3 and MRB perform functional checks of the 
fire protection in accordance with current regulations.  
3d party panels also possible. Please check compability first. 
See www.bevent-rasch.se for further details.

Quick facts

•  Fire class EI90 / EI90S
•  Sizes from 200 x 200 mm to 800 x 800 mm 
•  Fitted safety actuator 24 V or 230 V
•  Low weight
•  Easy installation 
•  CE-marked building product in acc. with  
  EN 15650:2010
•  Available in MagiCAD

Use

Damper in combination with walls or floors for ventilation 
fire protection in buildings. In accordance with the har-
monised European Standard EN 15650:2010. In designs 
 according to associated documents, installation instruc-
tions and when the damper is used in combination with 
smoke detectors and monitoring system (MRB, MRB3, 
FENIX), or the like, the spread of fire/combustion gases 
is prevented. No further action against the spread of fire/
combustion gases is required.

Performance

CoCP (Certificate of Constancy  
of Performance) EN 15650:2010

0402-CPR-SC1299-13

Classification of fire resistance  
in accordance with EN13501-3

EI90 (ve ho i <–> o) S 

For complete classification,  
refer to the Performance Declaration.