background image

REFRIGERATION SYSTEM

The Refrigeration System consists of a hermetically sealed compressor and finned evaporator and condenser.

CONDENSER

The condenser has wide finned spaces which allow more air passage with less dirt or dust accumulation. The condenser

still requires periodic cleaning for maximum efficiency.

CONDENSER FAN MOTOR

The condenser fan motor assembly is mounted between the condenser and compressor. Air is drawn through the

condenser, over the body of the compressor and then out the rear of the unit compartment.

The motor is wired to cycle with the compressor but will continue to operate should the compressor cut out on the overload.

(The motor is permanently lubricated; therefore, oiling is not required).

DRIER

The drier is installed in the system just before the capillary tube. Its purpose is to trap minute particles of foreign material

and absorb any moisture in the system.

LIQUID CONTROL AND HEAT EXCHANGE

Liquid refrigerant control to the evaporator of the system is accomplished by the use of a capillary tube or expansion valve.

This capillary tube or liquid line is soldered to the suction line to form a heat exchanger which subcools the liquid refrigerant to
maintain high efficiency within the system.

REFRIGERATION SERVICE EVACUATION

Moisture in a refrigeration system is directly or indirectly the cause of more problems and complaints than all other factors

combined.

When large amounts are present, system freeze ups will occur. Even in minute amounts, moisture will combine with

refrigerants to form hydrochloric acid. The corrosive action of this acid forms sludge which will plug the lines and drier.

Since most field type vacuum pumps cannot pull a low enough vacuum to remove moisture from the system, it is

recommended that the system be triple evacuated, breaking each time with dry refrigerant nitrogen. Use care to purge air from
the charging hose when breaking the vacuum.

CHARGING REFRIGERATION SYSTEM

Since capillary tube systems have small critical refrigerant charges, we recommend that a field charge either be weighed in

or put in from a portable charge board. After maximum vacuum has been obtained as detailed above, attach charging cylinder
to the suction line making sure to purge air from hose with refrigerant. With the unit running, allow refrigerant to run slowly into
the system until the desired charge is reached. When using Refrigerant Blends it is recommended to liquid charge into the
high side of the system with the initial charge and then any remaining charge can be put into the suction side; however, care
must be taken to meter the remaining amount into the low side so as not to cause excess liquid to go to the compressor

              OVERCHARGE

                    UNDERCHARGE

When the cabinet has pulled down to operating

An undercharge or shortage of refrigerant will

temperature an indication of an overcharge is that

result in any or all of the following:

the suction line will be cooler than normal with the

1. Lower than normal head pressure.

compressor running. Running time will be higher

2. Lower than normal suction pressure.

than normal. Suction line will sweat or frost.

3. Excessive or continuous operation of compressor.
4. Higher than normal cabinet temperature.

Purge excessive refrigerant from the system very
carefully in small amounts waiting several minutes
for the system to balance.

FEDERAL LAW REQUIRES THAT REFRIGERANTS BE RECOVERED PRIOR TO SERVICING.

BEVERAGE-AIR

         ILA-1591  REV B-SHT 2

REFRIGERATION

SYSTEM

SERVICE AND
ANALYSIS CHART

Summary of Contents for BZ13 Series

Page 1: ...nspection includes complete refrigeration system cabinet construction finish IMPORTANT PLEASE RETAIN FOR YOUR RECORDS SALES OFFICE P O BOX 5932 SPARTANBURG S C 29304 5932 PHONE 864 582 8111 TOLL FREE 1 800 845 9800 TECHNICAL SERVICE 1 800 684 1199 PARTS ORDER FAX 1 800 262 9381 PLANTS SPARTANBURG S C BROOKVILLE PA HONEA PATH S C 809 062A rev B ...

Page 2: ...ly adjustable to suit package size and presentation requirements Interior cooling airflow performance should be considered when establishing shelf to product spacing An equal spacing of shelves with no less than 1 2 54 cm between top surface of product and bottom surface of shelf top is recommended To ensure proper airflow product must not extend beyond the front or rear edge of the shelving and m...

Page 3: ... maintain acceptable compressor operating temperature and efficient refrigeration system operation the condenser must be cleaned periodically Cleaning intervals will vary according to cabinet proximity to customer traffic location cleanliness humidity etc After initial unit placement it is recommended that the condenser face be inspected for blockage every other month until the need for cleaning i...

Page 4: ......

Page 5: ...cation mark cannot be seen Physically verify that the lamp has been rotated and locked into place See pictures below Caution Improperly installed lamps may cause damage to the lighting circuit Beverage Air shall have no liability whatsoever for equipment or component failures or other damages or losses which arise as a result of improper installation Bi pin lamp end identification mark Pins may no...

Page 6: ......

Page 7: ......

Page 8: ......

Page 9: ...l setting 1 Loose parts or mountings 2 Tubing rattle 3 Bent fan blade causing vibration 4 Fan motor bearings worn SOLUTION 1 Plug in line cord 2 Replace fuse 3 Refer to electrical section 4 Repair or replace control 5 Check wiring against diagram 1 Check wiring against diagram 2 Determine reason and correct 3 Determine reason and replace 4 Determine reason and correct replace if necessary 1 Determ...

Page 10: ...ince most field type vacuum pumps cannot pull a low enough vacuum to remove moisture from the system it is recommended that the system be triple evacuated breaking each time with dry refrigerant nitrogen Use care to purge air from the charging hose when breaking the vacuum 왎 CHARGING REFRIGERATION SYSTEM Since capillary tube systems have small critical refrigerant charges we recommend that a field...

Page 11: ...SERVICE RECORD ...

Reviews: