background image

MALFUNCTION

Compressor will
not start — no hum

Compressor will not
start — hums but trips
on overload protector

Compressor starts,
but does not switch
off of start winding

Compressor starts
and runs, but short
cycles on overload
protector

Unit runs OK,
but short cycles

Unit operates long
or continuously

Start capacitor open,
shorted or blown

Run capacitor open,
shorted or blown

Relay defective
or burned out

Space temperature
too high

Cooler freezing
beverage

Unit noisy

POSSIBLE CAUSE

1. Line cord not plugged in.
2. Fuse removed or blown.
3. Overload protector tripped.
4. Control stuck in open position.
5. Wiring improper or loose.

1. Improperly wired.
2. Low voltage to unit.
3. Starting capacitor defective.
4. Relay failing to close.

1. Low voltage to unit.
2. Relay failing to open.
3. Run capacitor defective.
4. Compressor motor has a winding open or
    shorted.

1. Additional current passing through
    overload protector.
2. Low voltage to unit.
3. Overload protector defective.
4. Run capacitor defective.
5. Excessive discharge pressure.
6. Compressor too hot — return gas hot.

1. Overload protector.
2. Cold control.
3. Overcharge.
4. Air in system.
5. Undercharge.

1. Shortage of refrigerant.
2. Control contacts stuck or frozen closed.
3. Evaporator coil iced.
4. Restriction in refrigeration system.
5. Dirty condenser.

1. Relay contacts not opening properly.
2. Low voltage to unit.
3. Improper relay.

1. Improper capacitor.
2. Excessively high line voltage.
    (110% or rated-max.).

1. Incorrect relay.
2. Line voltage too high or too low.
3. Relay being influenced by loose vibrating
    mounting.

1. Control setting too high.
2. Improper overcharge.
3. Inadequate air circulation.

1. Control setting.

1. Loose parts or mountings.
2. Tubing rattle.
3. Bent fan blade causing vibration.
4. Fan motor bearings worn.

SOLUTION

1. Plug in line cord.
2. Replace fuse.
3. Refer to electrical section.
4. Repair or replace control.
5. Check wiring against diagram.

1. Check wiring against diagram.
2. Determine reason and correct.
3. Determine reason and replace.
4. Determine reason and correct,
    replace if necessary.

1. Determine reason and correct.
2. Determine reason and correct,
    replace if necessary.
3. Determine reason and replace.
4. Replace compressor.

1. Check wiring diagram. Check for
   added fan motors. pumps, etc.,
   connected to wrong side of protector.
2. Determine reason and correct.
3. Check current, replace protector.
4. Determine reason and replace.
5. Check ventilation, restrictions in
   cooling medium, restrictions in
   refrigeration system.
6. Check refrigerant charge (fix leak)
    add if necessary

1. Check wiring diagram.
2. Differential set too close — widen.
3. Reduce refrigerant charge.
4. Purge and recharge.
5. Fix leak, add refrigerant.

1. Fix leak, add charge.
2. Clean contacts or replace control.
3. Defrost.
4. Determine location and remove.
5. Clean condenser.

1. Clean contacts or replace relay
    if necessary.
2. Determine reason and correct.
3. Replace

1. Determine correct size and replace.
2. Determine reason and correct.

1. Check and replace.
2. Determine reason and correct.
3. Remount rigidly.

1. Reset control.
2. Purge.
3. Improve air movement.

1. Reset control.

1. Find and tighten.
2. Reform to be free of contact.
3. Replace blade.
4. Replace motor.

ALL SERVICING MUST COMPLY WITH STATE AND FEDERAL REGULATIONS

SALES OFFICE: P.O. BOX 5932, SPARTANBURG, SOUTH CAROLINA 29304

PLANTS: SPARTANBURG, SOUTH CAROLINA • HONEA PATH, SOUTH CAROLINA

BROOKVILLE, PENNSYLVANIA

PHONE 803-582-8111        TOLL FREE NUMBER 1-800-845-9800

SERVICE AND
ANALYSIS CHART

REFRIGERATION

SYSTEM

ILA-1591 REV.B SHT 1

Summary of Contents for BZ13 Series

Page 1: ...nspection includes complete refrigeration system cabinet construction finish IMPORTANT PLEASE RETAIN FOR YOUR RECORDS SALES OFFICE P O BOX 5932 SPARTANBURG S C 29304 5932 PHONE 864 582 8111 TOLL FREE 1 800 845 9800 TECHNICAL SERVICE 1 800 684 1199 PARTS ORDER FAX 1 800 262 9381 PLANTS SPARTANBURG S C BROOKVILLE PA HONEA PATH S C 809 062A rev B ...

Page 2: ...ly adjustable to suit package size and presentation requirements Interior cooling airflow performance should be considered when establishing shelf to product spacing An equal spacing of shelves with no less than 1 2 54 cm between top surface of product and bottom surface of shelf top is recommended To ensure proper airflow product must not extend beyond the front or rear edge of the shelving and m...

Page 3: ... maintain acceptable compressor operating temperature and efficient refrigeration system operation the condenser must be cleaned periodically Cleaning intervals will vary according to cabinet proximity to customer traffic location cleanliness humidity etc After initial unit placement it is recommended that the condenser face be inspected for blockage every other month until the need for cleaning i...

Page 4: ......

Page 5: ...cation mark cannot be seen Physically verify that the lamp has been rotated and locked into place See pictures below Caution Improperly installed lamps may cause damage to the lighting circuit Beverage Air shall have no liability whatsoever for equipment or component failures or other damages or losses which arise as a result of improper installation Bi pin lamp end identification mark Pins may no...

Page 6: ......

Page 7: ......

Page 8: ......

Page 9: ...l setting 1 Loose parts or mountings 2 Tubing rattle 3 Bent fan blade causing vibration 4 Fan motor bearings worn SOLUTION 1 Plug in line cord 2 Replace fuse 3 Refer to electrical section 4 Repair or replace control 5 Check wiring against diagram 1 Check wiring against diagram 2 Determine reason and correct 3 Determine reason and replace 4 Determine reason and correct replace if necessary 1 Determ...

Page 10: ...ince most field type vacuum pumps cannot pull a low enough vacuum to remove moisture from the system it is recommended that the system be triple evacuated breaking each time with dry refrigerant nitrogen Use care to purge air from the charging hose when breaking the vacuum 왎 CHARGING REFRIGERATION SYSTEM Since capillary tube systems have small critical refrigerant charges we recommend that a field...

Page 11: ...SERVICE RECORD ...

Reviews: