Safety
2-7
2.5.3
Testing in keeping with the German Work-
place Safety Ordinance (BetrSichV)
In case of the coupling or installation of devices from vari-
ous manufacturers or suppliers, the operating company
has to carry out a precise test, prior to start-up, in keeping
with the German Workplace Safety Ordinance (BetrSichV)
in force and the applicable electrical regulations.
In case of queries, please get in touch with BFI Automa-
tion.
2.5.4
Safety test
In order to ensure correct operation, the flame scanners
as well as flame amplifiers of all applications have to be
tested several times by starting and stopping the burner
several times. In all cases the flame relay has to be
switched off reliably in case of an absent flame. Carry out
this test whilst several neighbouring burners are started
and stopped and different boiler outputs are used. This is
an indispensable pre-requisite for a safe and correct op-
eration of the device !
Summary of Contents for 2.0L
Page 2: ...ii...
Page 20: ...Safety 2 8...
Page 40: ...Description 5 2...
Page 42: ...Operation of the flame scanner 6 2...
Page 44: ...Maintenance and servicing 7 2...
Page 46: ...Failures 8 2...
Page 48: ...Order data 9 2...
Page 50: ...Accessories 10 2...
Page 51: ...Accessories 10 3...