background image

 

CI-1 Rear 

Connections 

There are four main interconnection paths to the rear panel: 

 

Conections to the fire detection system (CIE) 

 

Connections from external devices for fault indications 

 

Connections to the LSI-16(e) 

 

Power supply connections 

 

Each of these connection paths has several circuits as detailed below. 

 

 

 

CIE (Fire Detection System) Connections 

Isolated Ground provides a circuit return that is not directly connected to the CI-1 and LSI-16(e) Ground. 

Alarm inputs 1 through 4 are signals form the fire detection system. These signals place the Vocia system 
into an emergency mode according to the configuration determined for the input in Vocia software. The 
Alarm Reset Input cancels all active alarms in the system while the Alarm Silence Input maintains all 
active alarms but causes emergency messages to be silenced. The CI-1 provides the necessary 
terminating resistors for each input. Inputs are asserted by a positive transition to 12-24V with respect to 
the ‘Isolated Ground’ connection. This transition should preferably be derived from a dry contact closure 
to a remote 12V-24V source, or to the CI-1 24V Reference Out. 

The Voice Alarm Active output is provided to signal to the fire detection system that the Vocia system has 
been activated in emergency mode in response to an Alarm Input. A constant output denotes that an 
emergency message is playing. A pulsed output (1.25Hz) indicates that an alarm is active but emergency 
messages have been silenced. 

The General Fault Output is provided to signal to the fire detection system that there is a fault in the Vocia 
system that could affect delivery of an emergency message. 

The Voice Alarm Active and General Fault outputs pull low (to ground) when active. The outputs are 
monitored by the LSI-16(e) for open-circuit or short-circuit to ground or power supply and for over-voltage 
on the output pin (>35V DC). If incorrect conditions are detected a Fault is signaled. Output monitoring 
facilitates compliance with voice evacuation standards. For monitoring purposes, a load (maximum 22k

must be connected between each output and a positive voltage source referenced to the LSI-16(e) 
Ground, at the far end of the connection to the CIE (i.e. at the CIE). An LED indicator connected through 
a resistor to a positive voltage at the CIE will suffice as a monitoring load. 

Note that the LSI-16(e) provides a 10V source at the '10V Out' terminal on the LSI-16(e). Outputs may be 
pulled up at this source; however, the total current drawn from the source must not exceed 100mA. If an 
external voltage source is used for the outputs, it must not exceed 35V DC and in addition to the output 
loads, must also be connected to the LSI-16(e) ‘External Supply Overvoltage Monitor’ input (refer to LSI-
16(e) User Manual) for monitoring purposes. Due to monitoring constraints, it is not possible to use both 
the LSI-16(e) internal 10V source and an external source. 

 

 

Summary of Contents for Vocia CI-1

Page 1: ...CI 1 OPERATION MANUAL May 2019 585 0279 90B ...

Page 2: ...CI 1 Product Description The CI 1 Control Interface is a companion product to the Vocia LSI 16 Life Safety Interface It facilitates necessary connections to the LSI 16 LSI 16e to meet EN 54 16 standards ...

Page 3: ...r alarm condition This is normal operation For correct fault free operation inputs and outputs must be connected to the LSI 16 e and CI 1 or external equipment as detailed in this manual Installation Install the unit away from heat sources such as vents and radiators and in rooms with adequate ventilation Ensure that air can circulate freely behind beside and above the unit Do not exceed the maxim...

Page 4: ...ted the sounder will restart Press and hold the switch for two seconds to operate System Test Switch This switch will initiate a test sequence on the LSI 16 e All indicators in use on the LSI 16 e will light briefly and the sounder in the CI 1 will sound briefly thus confirming that essential annunciators are functional Press and hold the switch for two seconds to initiate the test sequence System...

Page 5: ...ncy message is playing A pulsed output 1 25Hz indicates that an alarm is active but emergency messages have been silenced The General Fault Output is provided to signal to the fire detection system that there is a fault in the Vocia system that could affect delivery of an emergency message The Voice Alarm Active and General Fault outputs pull low to ground when active The outputs are monitored by ...

Page 6: ... need an external pull up Connections to LSI 16 e These circuits are provided on Four five position plug in barrier strip connections One three position plug in barrier strip connector One DC barrel jack Circuit connections may be made by directly connecting pin for pin to the vertically adjacent connector Short interlinking cables are provided with the CI 1 for this purpose Refer to the LSI 16 e ...

Reviews: