background image

Connections from External Devices for Fault Indications 

These circuits are provided on a single five-position plug-in barrier strip connector. All Inputs are fully 
isolated from the CI-1 and LSI-16(e) internal circuits. The Isolated Ground provides a circuit return that is 
not directly connected to the CI-1 and LSI-16(e) Ground. 

These inputs allow the signaling of faults from external devices to the Vocia system so it may indicate and 
log faults that could affect emergency operation. These fault signals are typically derived from contact 
closures on external devices. For multiple devices (e.g. Multiple UPS units), fault contacts from each 
device may be ‘wired-OR’ connected (in parallel) to the fault input. UPS fault inputs are typically derived 
from UPS units used in the system (e.g. for backup powering of Vocia Amplifier units). PSU fault inputs 
are typically derived from battery backed power supplies used to power parts of a Vocia system.  

EWS PSU fault inputs are derived from optional emergency microphones (EWS-x) to indicate loss of 
power supply. Ethernet fault inputs are derived from fault contacts of industrial Ethernet switches used in 
critical parts of a Vocia system. All fault inputs are asserted by connecting the relevant pin to Isolated 
Ground. The UPS Fault, PSU Fault and EWS PSU Faults must be connected to 24V when non-asserted 
either by direct connection or through pull-up resistor (maximum 2.2k

). The 24V reference voltage 

output on the power supply connector may be used for this purpose. The Ethernet Fault input is pulled up 
internally and does not need an external pull up. 

 

Connections to LSI-16(e) 

These circuits are provided on: 

 

Four five position plug in barrier strip connections 

 

One three position plug in barrier strip connector 

 

One DC barrel jack. 

 

Circuit connections may be made by directly connecting pin-for-pin to the vertically adjacent connector. 
Short interlinking cables are provided with the CI-1 for this purpose. Refer to the LSI-16(e) Operation 
Manual for the circuit functions of these connectors. 

Note that the LSI-16(e) PSU Fault, Protection Fault and Path Fault outputs are connected to the CI-1 
purely for the purpose of providing required monitoring resistors (these outputs are not otherwise used by 
the CI-1). If these outputs are required for remote fault indications, the relevant connections should be 
removed from the Monitored Outputs connector of the LSI-16(e). As described in the LSI-16(e) Operation 
Manual, and external monitoring resistor will be required if these circuits are used. 

 

Power Supply Connections 

These circuits are provided on a single five-position plug-in barrier strip. Inputs are provided for two 24V 
power supply circuits to drive the LSI-16(e). This facilitates standards compliance by providing a means of 
redundant connections. 

Each power supply must be capable of 24V DC at 15Watts. The Ground 1 and Ground 2 connections are 
internally connected together and to system ground. The VRef connection may be used as a voltage 
source for pull-ups on required fault inputs. This output is current limited at 100mA. 

Loss of power to either power supply input will result in the LSI-16(e) detecting a fault. If standards 
compliance is not required for an installation, a single power supply connection must be paralleled to the 
two power supply inputs to avoid generating a fault signal. 

Summary of Contents for Vocia CI-1

Page 1: ...CI 1 OPERATION MANUAL May 2019 585 0279 90B ...

Page 2: ...CI 1 Product Description The CI 1 Control Interface is a companion product to the Vocia LSI 16 Life Safety Interface It facilitates necessary connections to the LSI 16 LSI 16e to meet EN 54 16 standards ...

Page 3: ...r alarm condition This is normal operation For correct fault free operation inputs and outputs must be connected to the LSI 16 e and CI 1 or external equipment as detailed in this manual Installation Install the unit away from heat sources such as vents and radiators and in rooms with adequate ventilation Ensure that air can circulate freely behind beside and above the unit Do not exceed the maxim...

Page 4: ...ted the sounder will restart Press and hold the switch for two seconds to operate System Test Switch This switch will initiate a test sequence on the LSI 16 e All indicators in use on the LSI 16 e will light briefly and the sounder in the CI 1 will sound briefly thus confirming that essential annunciators are functional Press and hold the switch for two seconds to initiate the test sequence System...

Page 5: ...ncy message is playing A pulsed output 1 25Hz indicates that an alarm is active but emergency messages have been silenced The General Fault Output is provided to signal to the fire detection system that there is a fault in the Vocia system that could affect delivery of an emergency message The Voice Alarm Active and General Fault outputs pull low to ground when active The outputs are monitored by ...

Page 6: ... need an external pull up Connections to LSI 16 e These circuits are provided on Four five position plug in barrier strip connections One three position plug in barrier strip connector One DC barrel jack Circuit connections may be made by directly connecting pin for pin to the vertically adjacent connector Short interlinking cables are provided with the CI 1 for this purpose Refer to the LSI 16 e ...

Reviews: