BY-PASS VALVE
16 BY-PASS VALVE
16 .1 Function
The By-pass valve "A" in Figure 16.1 is located between the C.H.
water flow and return and its function is that of guaranteeing a
minimum flow across the primary heat exchanger if the circula
-
tion across the C.H. system is completely closed.
The By-pass valve is fitted on the rear side of the diverter group.
Figure 16 .1
A
16 .2 Removal
Warning: isolate the boiler from the mains electrici-
ty supply before removing any covering or compo-
nent .
1 Remove all the case panels.
2 Empty the primary circuit of the boiler.
3 Unscrew the screws "B" and pull the by-pass valve "A" (Fig-
ure 16.2).
Figure 16 .2
B
A
4 Reassemble the by-pass valve as illustrated in Figure 16.2
reversing the order of removal.
Warning: to lubricate the O-ring gaskets exclusively
use a silicone base grease compatible to be in con-
tact with foods and approved by the local water Au-
thorities .