background image

Main electronic control/ignition p.c.b.

17

6.7

Thermal control in the ”c.h.” mode

lock memorised?

Switch in the c.h. function mode

Request for heat from

room thermostat?

circulator off

fan still

circulator on

Is primary circuit

temperature higher than that

selected?

YES

Temp. difference

between probes

higher than 35

˚

C ?

NO

YES

NO

starts fan

checks fan rpm

YES

cancels lock

Is fan rpm

exact?

NO

YES

Is flue

temperature higher than 110

˚

C?

YES

NO

beginning of wait period

flame presence?

End of wait

period?

YES

NO

YES

starts ignition discharges

Opens gas valve

beginning of ignition period

flame presence?

YES

interrupts ignition discharges

gas valve open

fan runs

End of ignition

period?

NO

NO

YES

closes gas valve

stops fan

interrupts ignition discharges

memorizes lock

display show lock---out

reset key

pressed?

flame presence?

NO

NO

Is fan rpm

exact?

YES

NO

safety thermostat or flue

temperature probe lock out?

YES

NO

YES

YES

stop circulator (3min)

YES

NO

NO

Fig. 6.12

Summary of Contents for Activ A 12OV

Page 1: ...odels G C Appl No Activ A 12OV Activ A 15OV Activ A 20OV Activ A 25OV Leave this manual adjacent to the gas meter Warning Service repairs must be carried out only by a qualified Gas Safety Registered...

Page 2: ...tion 18 7 2 Normaly information 18 7 3 Info modality 19 7 4 Function modes setting modality 19 7 5 Removal of the control panel electr p c b 19 8 Gas valve 21 8 1 Function 21 8 2 Description of the pa...

Page 3: ...Ighition electrodes Burner Fan Air box air gas mixer Pipe silencer Electronic control box Condensate trap C h pressure relief valve Condensing heat purger valve Control panel Gas valve Gas restrictor...

Page 4: ...e boiler Pull the lower part of the front panel and lift it upwards Fig 2 3 C C Fig 2 3 To remove the side panels loosen the screws B Fig 2 2 and C Fig 2 3 Pull the side panels towards the outside To...

Page 5: ...ted into main electronic p c b box proceed as follows 1 Remove the front panel of the case Terminal block lid removal 2 To remove the terminal block lid E Fig 2 7 free the front hooks E Fig 2 7 3 Slig...

Page 6: ...ht panels of the boiler 3 Open the drain tap F Fig 2 10 until the boiler is completely emptied F CLOSED OPEN Fig 2 10 4 To help the draining of the primary circuit loose the condensing heat exchanger...

Page 7: ...h flow temp probe NTC probe Condensate trap bu bn bu bn og vt bu bn bk bk rd rd bu gnye bn ye vt bn brown bu blue bk black wh white rd red og gy grey gn green ye yellow vt violet og orange gnye green...

Page 8: ...Diagrams 6 3 2 Circuit voltages 230 Electrical voltages with burner on during c h operation 230 Safety thermostat 0 Fan Supply network 230 C h external 230 Gas valve pump...

Page 9: ...Boiler settings Control panel electr p c b Gas valve C h flow temp probe C h return temp probe Fan air restrictor Ignition electrode Detection electrode Safety thermostat Gas restrictor Flue temp prob...

Page 10: ...ty valve when the boiler is off J J J Lock out is indicated as Er on the display Note Useful information can be obtained also from the optical indication given by the appliance display see section 4 1...

Page 11: ...tted Er 09 Faulty flue temperature probe NTC Er 10 RESET Lockout flue temperature probe NTC Flue temperature 120 C Er 14 RESET Faulty pump absence of water flow in the main circuit or primary temperat...

Page 12: ...els see section 2 3 Disconnect the flue system from the boiler 4 Disconnect the air manifold D Fig 5 4 by pulling it 5 Disconnect the rubber pipe E Fig 5 2 6 Unscrew the gas connectors F 7 Remove gas...

Page 13: ...24 Remove the Condensing heat exchanger slightly move it upwards turn it frontwards freeing it from the below screws X Fig 5 4 Fig 5 2 and then extract it forwards 25 Reassemble the Condensing heat e...

Page 14: ...ted and supplies the fan regu lating its speed The Main electronic control ignition p c b has a safety function and any incorrect interventions or tampering can result in conditions of dangerous funct...

Page 15: ...is converted into an elec tric signal by means of temperature probes The user setting the desired temperature with the con trol panel p c b key If the power requested is lower than 40 of the maxi mum...

Page 16: ...ollowing table gives details of each parameter and the possible value that can be set Important at the end of the setting operation it is im portant to fill update the table in the installation manual...

Page 17: ...Pr 27 25 45 factory set 25 C Tab 6 1 6 5 Checks n Check that the fuses are complete If the Main electronic control ignition p c b does not supply any device pump fan etc check that the fuses 10 Fig 6...

Page 18: ...s in the reverse order Important When re assembling the Main electronic control igni tion p c b 7 It is not necessary to utilise static protections but it is advisable to ensure that the pcb is handle...

Page 19: ...exact NO YES Is flue temperature higher than 110 C YES NO beginning of wait period flame presence End of wait period YES NO YES starts ignition discharges Opens gas valve beginning of ignition period...

Page 20: ...be interven lockout Er 14 RESET Faulty pump or primary tempera ture above 105 C Er 15 RESET None or too low water flow Faulty pump temp difference between probes higher than 35 C Er 16 RESET Possible...

Page 21: ...e INFO mode hold keys A and C Fig 7 1 pressed at the same time The following table gives details of each parameter and the possible value that can be show Description Parameter Value External temperat...

Page 22: ...screws B 5 Delicately flex the hooks C in the directions indi cated Fig 7 3 in order to release the circuit from the box 6 Remove the Control panel electronic p c b 7 Reassemble the Control panel elec...

Page 23: ...electricity supply to the boiler switch ing on the fused spur isolation switch 6 Set the boiler in c h function as illustrated in Fig 8 3 C h function Fig 8 3 7 Make sure that the room thermostat is...

Page 24: ...tion 18 Allow the analyser to give a stable reading 19 Read the CO2 value It should be between Model Type gas CO2 value range Activ A 12OV A ti A 15OV Natural G20 8 2 9 0 Activ A 15OV Propane G31 9 2...

Page 25: ...he electrical connector 4 Fig 8 2 3 Measure the electrical resistance between the connector pins of the on off operators as illus trated in Fig 8 11 ON OFF Operator approx 920 ON OFF Operator approx 6...

Page 26: ...d in section 8 3 After any service operation on the components of the gas circuit check all the connections for gas leaks Warning After cleaning or replacement as detailed above it is deemed necessary...

Page 27: ...ctricity supply before removing any covering or component Disconnect the cable from the Temperature probe Measure the temperature of the pipe C c h flow Tem perature probe Fig 9 3 or of the pipe D c h...

Page 28: ...Temperature probe 26 D F B Fig 9 4...

Page 29: ...er pipe C Fig 10 2 4 Unscrew the gas connectors D and remove the gas pipe E 5 Disconnect the connector F 6 Disconnect the fan connector G by pressing the plastic hook placed on the side of the connect...

Page 30: ...electrodes carrying out the removal operation in reverse or der 11 3 Removal of the burner Warning isolate the boiler from the mains electricity supply before removing any covering or component 1 Remo...

Page 31: ...Ignition and detection electrodes 29 Ignition electrode 3 5 mm earth electrode Fig 11 4 n Check the connection wires...

Page 32: ...ntain a tem perature below that of the safety thermostat and no overheat intervention should occur Warning isolate the boiler from the mains electricity supply before removing any covering or componen...

Page 33: ...covering or component 1 Remove all the case panels 2 Disconnect the connector B from the Flue tem perature probe NTC by pressing the plastic hook placed on the side of the connector 3 Unscrew and rem...

Page 34: ...e cleanness of the trap 1 Unscrew the screws B and remove the plate C Fig 14 2 B C Fig 14 2 Unscrew the plug D on the bottom of the trap A and re move dirt eventually deposit Fig 14 3 14 3 Removal War...

Page 35: ...Activ A 25OV 1 BI1462 102 3 Fan 1 BI1313 102 4 Gas valve 1 BI1313 103 SIT 848 Sigma 0848135 5 Main Electronic control ignition p c b 1 BI2035 113 6 Control panel electronic p c b 1 BI2035 101 7 Tempe...

Page 36: ...1796220170 17962 2017 0 1710 36A4 UK Biasi UK Ltd Commercial Road Leamore Enterprise Park WALSALL WS2 7NQ Tel 01922 714600 www biasi co uk 29 04 2010 N...

Reviews: