background image

Electronic control p.c.b.

19

A short pulse every 4 seconds

Boiler in stand---by condition.

(function control in

position).
Anti---freeze system active.

1 second ON 1 second OFF

Boiler ON condition

(function control in

or

position)

With the boiler switched ON (

or

) all the lamps

(7 in Fig. 29) are activated.

The following table gives the relationship between each

of the possible lamp combinations and their meaning.

Normally operating boiler

(see the previous table for details)

C.h. operation

D.h.w. operation

Frost protect operation

D.h.w. operation

Excessive temperature on primary circuit

Faulty c.h. temperature probe NTC

Faulty d.h.w temperature probe NTC

Faulty primary circuit

(no water or absence of flow)

Lack of burner ignition (no ignition signal from

the full seqence ignition device)

Ignition gas pressure adjustment

Minimum gas pressure adjustment

Lack of power supply or fauly electronic

control p.c.b. *

Fauly electronic control p.c.b. *

Lamp

OFF

Lamp

ON

Flashing lamp, alone

or simultaneously

with an other lamp.

Flashing lamp,

alternate with

another lamp.

* These conditions are normal only for a short time when the

power supply is applied to the boiler.
If permanent they indicate a faulty p.c.b.

10.5

Dip---switch selectors

The function selectors 8 (Fig. 29 and Fig. 32) are micro-

switches with which it is possible to select the various

boiler control function modes.

In Fig. 32 the selectors are illustrated in the configur-

ation in which the boiler is set in the factory (natural gas

boiler).

ON (1)

OFF (0)

1 2 3 4

8

Gas conversion
Ignition gas pressure adjustment
Reignition frequency

Minimum gas pressure adjustment

Fig. 32

f

Selector 1

This forces the boiler to operate at the minimum gas

pressure in order to allow the adjustment of the mini-

mum gas pressure at the burner (on the modulation op-

erator of the gas valve).
After any adjustment operation the selector has to be

brought back to the normal position (ON).

f

Selector 2

This selects the boiler functions on the basis of the type

of gas used.
It allows the selection of the maximum supply current

given to the modulator device.
To set selector 2 correctly follow the table in Fig. 33.

Gas supply

Position of selector

Approx. Max current

through the modu-

lator device

Natural gas

On

120 mA

L.P.G.

Off

165 mA

Fig. 33

f

Selector 3

This forces the functioning of the boiler in order to allow

the optimal gas pressure at the burner to be adjusted

during the ignition phase.
The adjustment (see section 10.7) is done by means

of the potentiometer ”10” marked “ACC” (Fig. 29 on

page 17).
After the adjustment operations bring the selector back

to the normal position (ON).

gas pressure calibration

Normal

ON (1)

OFF (0)

Fig. 34

f

Selector 4

This allows you to select the minimum time that must

pass between two ignitions of the burner in c.h. func-

tion.

30 sec.

3 min.

ON (1)

OFF (0)

Fig. 35

Summary of Contents for GARDA HE M96.24SM/B

Page 1: ...igh efficiency gas boiler Service manual GARDA HE Models G C Appl No M96 24SM B 47 970 25 M96 28SM B 47 970 26 GARDA HE SILVER Models G C Appl No M96 24SM D 47 970 27 M96 28SM D 47 970 28 Leave this m...

Page 2: ...11 1 Function 23 11 2 Checks 23 11 3 Removal 23 11 4 Ignition and control sequence 24 12 Modulating gas valve 25 12 1 Function 25 12 2 Nomenclature of the parts 25 12 3 Adjustment 25 12 4 Checks 26 12...

Page 3: ...lease Pump D h w temp probe D h w heat exchanger Expansion vessel Detection electrode valve Condensing Diverter valve Air pressure switch Main circuit Flue thermostat heat exchanger Condensate trap fl...

Page 4: ...A Fig 2 lift the panel and remove it A Fig 2 To remove the side panels loosen the screws B and C Fig 3 bring the base of the panels away from the boiler and lift them freeing them from the top hooks B...

Page 5: ...d of the sealed chamber For this purpose remove the front and side panels of the case remove the screws G as indicated in Fig 6 and remove the lid 2 5 Emptying the primary circuit 1 Close the c h circ...

Page 6: ...low switch C h temperature probe NTC Electronic control p c b Full sequence ignition device gn green ye yellow rd bu wh rd bu rd bu bn bu bn bn bu bn bu bk bn bu 3 1 2 bk gnye bu rd bu bn gnye gnye gn...

Page 7: ...NTC Three way diverter valve gas valve DHW flow switch flow switch CH temperature probe NTC Electronic control p c b Full sequence ignition device gnye gnye bu gnye gy rd bu wh rd bu rd bu bn bu bn bn...

Page 8: ...L Transformer ACTIVE CIRCUIT INACTIVE CIRCUIT L LINE N NEUTRAL N Electronic control p c b low voltage section J1 2 J3 3 J3 5 J3 4 J3 2 J3 1 J2 4 J2 5 Three way diverter valve Pump Full sequence igniti...

Page 9: ...h operation only during d h w operation 230 230 230 0 Pump Full sequence Ignition device 3 way diverter valve 0 0 Electronic control p c b 230 230 Modulating Gas valve Safety thermostat 0 Fan 230 230...

Page 10: ...ration only during d h w operation 230 230 230 0 Pump Full sequence Ignition device 3 way diverter valve 0 0 Electronic control p c b 230 230 Modulating Gas valve Safety thermostat 0 Fan 230 230 0 Ele...

Page 11: ...Pressure gauge By pressing the reset push button the boiler turns on and operates correctly J J 6 J J J By pressing the reset push button the boiler starts the ignition cycle The burner doesn t light...

Page 12: ...e safety valve during operation on c h J J J J Water leaks from the safety valve when the boiler is off J J J Note Useful information can be obtained also from the optical indication given by the appl...

Page 13: ...it from the wiring E M C B F C D G I J N K L H Fig 11 7 Loosen the connection K and move the pipe L downwards freeing it from the connection of the primary het exchanger 8 Remove the clip M 9 Move th...

Page 14: ...see section 21 3 5 Completely loosen the connection G and slightly move the pipe H upwards 6 Remove the clip I and move the pipe J down wards freeing it from the connection then turn it towards right...

Page 15: ...re removing any covering or component 1 Remove the front and right hand side panels of the case 2 Empty the primary circuit and the d h w circuit of the boiler 3 Completely unscrew the two Allen key s...

Page 16: ...turn the rotor in the direc tion of the arrow If there is a defect in starting the rotor will begin to turn normally only starting it manually n Check that the impeller is integral with the rotor Wit...

Page 17: ...B brass spindle when the boiler operates in c h mode In both figures the relationship between the position of the actuator and the resistance of the motor windings the motor must be disconnected from...

Page 18: ...t both c h and d h w temperature probe respectively H and I 6 Unscrew the connector J the c h flow connector and the d h w outlet connector F G J H I Fig 25 7 Remove the d h w heat exchanger see secti...

Page 19: ...es inlet in formation coming from the boiler the sensors or from the outside knobs room thermostat etc processes it and consequently acts with outlet commands on other components of the boiler Fig 28...

Page 20: ...trol panel through the adjustment made by the user knob 75 C Fig 31 Normally the result of the comparison between these two signals directly operates the adjustment elements of the gas valve modulatio...

Page 21: ...le to select the various boiler control function modes In Fig 32 the selectors are illustrated in the configur ation in which the boiler is set in the factory natural gas boiler ON 1 OFF 0 1 2 3 4 8 G...

Page 22: ...ectronic control p c b does not supply any de vice pump fan etc check that the fuse 12 Fig 29 is complete If the fuse has blown replace it with one that has the same characteristics after having ident...

Page 23: ...ake sure the c h and d h w tem perature adjustment knobs can move freely for the complete range If not remove the spindle again as described at step 3 turn the knob half a turn and re insert the spind...

Page 24: ...or heat from room thermostat Starts the circulator Operates motorised valve Supplies the ignition device NO Circulator off Operates motorised valve Ignition device off YES YES Fig 40 10 11 Thermal con...

Page 25: ...r connection f Gas injectors blocked f Faulty modulation gas valve faulty on off oper ators or not electrically supplied f Faulty Full sequence ignition device Other components like the air pressure s...

Page 26: ...sure switch at work NO YES starts ignition discharges opens gas valve beginning of ignition period flame presence end of ignition period NO NO YES closes gas valve stops fan interrupts ignition discha...

Page 27: ...e input connect a suitable pressure gauge and check the gas pressure of the supply network 3 Remove the gauge and close the pressure test point 6 4 Open the gas valve outlet pressure test point 8 in F...

Page 28: ...case as explained in the section 2 3 of this manual 2 Disconnect the connector D Fig 47 3 Unscrew the screw E and remove on off oper ator coils 4 Reassemble the coils carrying out the removal operati...

Page 29: ...the switch box verify the position of the shaft B referring to Fig 50 B Boiler OFF Boiler ON Fig 50 n Electrical check It is possible to verify the general operation of the switch by measuring the ele...

Page 30: ...rrect value 14 3 Removal of the expansion vessel If there is at least 400 mm clearance above the boiler and the rear exit flue can be easily removed the expan sion vessel can be changed without removi...

Page 31: ...ssory 10 Threaded ring 1 2 3 4 5 6 7 8 9 10 Fig 59 15 3 Checks Warning isolate the boiler from the mains electricity supply before removing any covering or component n Flow switch sensor operation 1 R...

Page 32: ...tch sensor 1 and bring the ring in touch with the sensor as illustrated in Fig 61 4 Observe the lamp B placed on the sensor body that should light If not reverse the ring and repeat the previous opera...

Page 33: ...flow c h return d h w inlet d h w outlet A B Fig 63 16 2 Checks n Temperature resistance relationship Warning isolate the boiler from the mains electricity supply before removing any covering or compo...

Page 34: ...e is fitted on the rear side of the div erter group A Fig 65 17 2 Removal Warning isolate the boiler from the mains electricity supply before removing any covering or component 1 Remove all the case p...

Page 35: ...measure the electrical resistance of the motor that has to be about 43 W M96 24SM 25 W M96 28SM at ambient temperature D A C Fig 68 n Check of the Air pressure switch operation Warning isolate the bo...

Page 36: ...ls the sealed chamber lid and the combustion chamber lid 2 Disconnect the connectors D and the earth con nection E Fig 68 3 Disconnect the pipe which connect the venturi device to the Air pressure swi...

Page 37: ...manual B H I Fig 73 18 5 Removal of the Air pressure switch Warning isolate the boiler from the mains electricity supply before removing any covering or component 1 Remove all the case panels and the...

Page 38: ...e removing any covering or component 1 Remove all the case panels the sealed chamber lid and the combustion chamber lid 2 Check for the integrity of the insulation of wires which connect the electrode...

Page 39: ...cur Warning isolate the boiler from the mains electricity supply before removing any covering or component n Electrical function 1 Remove all the case panels and the lid of the sealed chamber 2 Remove...

Page 40: ...der a protective cap B in Fig 81 and can be re ached by unscrewing the cap The intervention of the Flue thermostat may be caused by a defective operation of the device but more probably is due to a po...

Page 41: ...ec trode Fig 84 C B Fig 84 If the drain pipe is plugged or in any case in which the condensate isn t correctly evacuated the condensate level in the trap rises putting in contact the electrodes thus c...

Page 42: ...E83 178 Combustion chamber side panels 2 BI1326 100 10 E83 180 Combustion chamber rear panel mod M96 24SM 1 BI1326 107 E83 181 Combustion chamber rear panel mod M96 28SM 1 BI1326 108 11 E83 196 Combus...

Page 43: ...Short spare parts list 41 1 2 6 4 5 7 3 8 15 18 12 13 20 22 23 24 26 27 14 16 25 17 19 9 10 11 9 21...

Page 44: ...796210720 17962 1072 0 2404 44A4 UK Biasi U K Ltd Unit 31 33 Planetary Road Industrial Estate Neachells Lane Willenhall Wolverhampton WV 13 3XB Technical helpline 01902 304 400 Web site www biasi co u...

Reviews: