- 37 -
D.h.w. flow switch, filter anD flow limiter
14 d .h .w . flOw switch, filter and flOw
limiter
14 .1 function
The d.h.w. flow switch
A in Figure 14.1 is a device that generates
an electrical signal when hot water is drawn.
figure 14 .1
a
When the flow rate through the d.h.w. circuit reaches about 2,5
litres/min’, the sensor closes the electric contact that switches
the boiler d.h.w operation ON.
14 .2 description and location of parts - (figure
14 .2)
1
Flow switch plug
2
O-ring
3
Flow limiter (Inovia 30C ERP. Inovia 35C ERP. optional ac-
cessory)
4
Body with flow meter turbine
5
Filter
figure 14 .2
2
1
3
4
2
5
14 .3 removal of the sensor
warning: isolate the boiler from the mains electrici-
ty supply before removing any covering or compo-
nent .
figure 14 .3
b
c
d
e
1 Remove the front panel of the case.
2 Disconnect the connectors B and remove the sensor holder
C (Figure 14.3).
3 Remove the sensor.
14 .4 checks
warning: isolate the boiler from the mains electrici-
ty supply before removing any covering or compo-
nent .
Sensor operation
figure 14 .4
wh = white
0..32 Hz
(without flow rate)
33..200 Hz
(witht flow rate)
rd
rd
5V
bu
bu
wh
wh
bu = blue
rd = red
b
1 Remove the front panel of the case.
2 Don't disconnect the connectors B
3 Measure the electrical frequency at the leads of the sensor.
Without flow rate the electrical frequency must be 0
÷32Hz
.
With flow rate the electrical frequency must be 33
÷200Hz
.