- 54 -
INST
ALLA
TION
INSTALLATION
length of the pipes by:
For the bend of 45° loss
0,9 m
For the bend of 90° loss
1,65 m
Fig. 6.10
90°
45°
Type C
53
C
63
TYPE
If using pipes and terminals by other manu-
facturers (Type C
63
), it is necessary that
these are approved and in the case of flue
pipes, it is necessary to use materials com-
patible with condensation products.
During the pipes dimensioning phase, take
into consideration the static pressure resi-
due of the fan:
Useful static pres-
sure at nominal heat
input
25 kW
90
Pa
30 kW
90
Pa
35 kW
90
Pa
Overheated flue
25 kW
93
°C
30 kW
98
°C
35 kW
98
°C
Maximum recircula-
tion of CO
2
in the
suction duct
25 kW
0,95
%
30 kW
0,95
%
35 kW
0,95
%
Roof flue exhaust kit (Fig. 6.11)
Coaxial pipe Ø 80/125 mm with a nominal
height of 0.96 m.
This kit exhausts directly to the roof.
Fig. 6.11
45°
90°
Ø 125
Type C
33
Extensions are available for reaching the
maximum height.
Its maximum height with extension is 10 m.
Bends of Ø 80 mm at 90° and at 45° are
available that reduce the maximum total
length of the pipes by:
For the bend of 45° loss
0,5 m
For the bend of 90° loss
1 m
Pluming kit (Fig. 6.12)
Co-axial ø 60/100 mm + vertical part ø 60
mm (flue outlet).
This kit allows the combustion air to be
sucked up and expel the burnt gases di-
rectly to the outside through a telescopic
co- axial flue (450-950 mm).