3. Insofar as practical, close all building doors and windows and all doors between the
space in which the appliance remaining connected to the common venting system are
located and other spaces of the building . Turn on any appliance not connected to the
common vent system. Turn on all exhaust fans except for summer exhaust fans. Close
the fireplace damper if applicable.
4. Place in operation the appliance being inspected. Follow the lighting instructions. Ad-
just thermostat so appliance will operate continuously.
5. Test for spillage at the barometric damper after 5 minutes of main burner operation.
Use the flame of a match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the common
venting system property vents when tested as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any other gas-burning appliance to their previous
condition of use.
7. Any improper operation of the common venting system should be corrected so the in-
stallation conforms with the National fuel Gas Code, ANSI Z223.1 and/or CAN/CGA
B149, Installation Codes. When resizing any portion of the common venting system,
the common venting system should be resized to approach the minimum size as deter-
mined using the appropriate tables in Part 11 of the National Fuel Gas Code, ANSI
Z223.1, and/or CAN/CGA B149, Installation Codes.
7.1 Common Exhaust Venting Cont.
1. Pierce a 5/8” hole into the vent pipe near the appliance outlet. Remove one of the securing
nuts from the pipe of the safety switch. Tighten the other securing nut onto the pipe as far
as possible.
2. Insert the threaded pipe end into the pierced hole, then install the securing nut, then install
the securing nut, which was removed in step 1, and tighten securely.
3. Please consult the wiring section of this manual for the wiring of the blocked flue switch.
7.2 Blocked Flue Switch:
Summary of Contents for SG 2
Page 2: ...Page 2 Biasi SG Series...
Page 26: ...Page 26 Biasi SG Series 12 1 Oil Burner Wiring...
Page 27: ...Biasi SG Series Page 27 12 1 Oil Burner Wiring...
Page 28: ...Page 28 Biasi SG Series 12 2 Gas Burner Wiring TO EARTH GROUND LINE HONEYWELL 7248U...
Page 29: ...Biasi SG Series Page 29 12 2 Gas Burner Wiring...
Page 37: ...Biasi SG Series Page 37 Notes...
Page 38: ...Page 38 Biasi SG Series Notes...
Page 39: ...Biasi SG Series Page 39 Notes...