Mount the 7248 control to the side of the
casing in the rear of the boiler. Position the
aquastat so that the sensor is able to reach the
immersion well installed in the back of the
boiler where it will be installed.
•
Run wire harness “A” under the top panel of
the boiler casing.
•
Connect the female connector from harness
“A” to the male connector of harness “B”.
•
Harness “C” connects to the burner. Run the
harness behind the front panel of the boiler
and connect it to the male harness on the
burner.
•
Bring line voltage into the power terminals of
the 7248 high limit aquastat.
•
Connect the “TT” terminals of the 7248 to the
end-switch on a external control or to a room
thermostat.
•
For more detail, please refer to the wiring
diagrams on the following pages.