UPSI-1208DPx
Revision 1-5
16
INTERFERENCE IMMUNITY ACCORDING TO EN 61000 (INDUSTRY)
Basic standard CE
Fulfilled requirements according to EN 61000 (CE)
(Interference immunity of industrial environment)
Electrostatic discharge
EN 61000-4-2
Contact discharge
Air discharge
Comment
4 kV
8 kV
Criterion B
Electromagnetic HF field
EN 61000-4-3
Frequency range
Test field strength
Frequency range
Test field strength
Comment
80 MHz … 1 GHz
10 V/m
1.4 GHz … 2 GHz
3 V/m
Criterion A
Fast transients (Burst)
EN 61000-4-4
Test voltage
Comment
2 kV
Criterion A
Surge voltage load (Surge)
EN 61000-4-5
Test voltage L–N
Test voltage L–PE, N–PE
Comment
±1 kV
±2 kV
Criterion A
Power frequency magnetic field immunity
EN 61000-4-8
Test level
Comment
30 A/m
Criterion A