41
English
UPSI-IP-1 series | UPSI- IP-2 series
UPSI-2406IP-12U / UPSI-2406IP-24U / UPSI-2406IP-26U
I
LOAD
[A]
I
CHARGE
[A]
I
IN TOTAL
[A]
P
IN TOTAL
[W]
0
3
3
72
1
3
4
96
2
2.7
4.7
113
3
2.5
5.5
132
4
2.2
6.2
149
5
2
7
168
6
1.5
7.5
180
Optional wide-range input: The UPS devices UPSI-1208IP-23UW, UPSI-2406IP-24UW and
UPSI-2406IP-26UW are equipped by an upstream DC/DC converter so that the input
current I
IN
can not be specified sweepingly. The input voltage varies between 7 or 8 and
36 V and so input current is changing correspondingly. Depending on the input and
output voltage, there is a power loss P
DC/DC
(converted into heat) of the DC / DC converter
of max. 10 % P
LOAD
, too. As a result, only the maximum input power P
IN TOTAL
can
be specified:
7/8…36 V
12 V or 24 V
12 V or 24 V
DC/DC converter
UPSI
Batterypack
Application
Input source
I
IN TOTAL
[A]
I
LOAD
[A]
I
CHARGE/DISCHARGE
[A]
I
LOAD
[A]