INTERFERENCE IMMUNITY ACCORDING TO 61000-6-2 (INDUSTRY SECTOR)
Basic standard CE
Normative minimum requirements EN 61000-6-2 (CE)
(Interference immunity of industrial environment)
Electrostatic discharge
EN 61000-4-2
Housing contact discharge
Housing air discharge
Comment
4 kV (test level 2)
8 kV (test level 3)
Criterion A
Electromagnetic HF field
EN 61000-4-3
Frequency range
Test field strength
Frequency range
Test field strength
Frequency range
Test field strength
Comment
80 MHz … 1 GHz
10 V/m (test level 3)
1.4 GHz … 2 GHz
3 V/m (test level 2)
2 GHz … 2.7 GHz
1 V/m (test level 1)
Criterion A
INTERFERENCE IMMUNITY ACCORDING TO EN 61000-6-2 (INDUSTRY SECTOR)
Basic standard CE
Normative minimum requirements EN 61000-6-2 (CE)
(Interference immunity of industrial environment)
Fast transients (Burst)
EN 61000-4-4
Input
Output
Signal
Comment
0.5 kV (test level 1 symmetrical)
0.5 kV (test level 1 symmetrical)
0.5 kV (test level 1 symmetrical)
Criterion A
Surge voltage load (Surge)
EN 61000-4-5
Input
Output
Signal
Comment
0.5 kV (test level 1 symmetrical)
0.5 kV (test level 1 symmetrical)
0.5 kV (test level 1 symmetrical)
Criterion A
Power frequency magnetic field immunity
EN 61000-4-8
Comment
Criterion A