E11  Behaviour in case of exceeding maximum backup time

When the given buffering times are exceeded, the output is separated on the basis of the discharge voltage of 
the corresponding storage medium (total discharge protection).
For supercapacitors, which are not sensitive to a deep discharge, a threshold has been definded which is limi-
ted by the current. The lower the voltage, the higher the current on the capacitors at constant output power.

If more than 70 % of the maximum allowable output current is consumed during discharge of the supercapa-
citors, the converter will shut down without immediately dis connecting the output and a lower voltage will 
appear at the output (state <2 s). This condition should be avoided by shutting down the system in time before 
discharging the supercapacitors under high currents.

E12  Status LED

1 x flash, pause 1,5 s

Status: Battery start

2 x flash, pause 1,5 s

Status: Capacity for start is required, state charging

3 x flash, pause 1,5 s

Status shutdown: Waiting for shutdown completion

4 x flash, pause 1,5 s

Status reboot: Output is switched off and time runs until restart (Reboot)

5 x flash, pause 1,5 s

Status: No battery recognized

6 x flash, pause 1,5 s

Battery voltage too high, battery disabled

7 x flash, pause 1,5 s

Charge current too high, battery disabled

1 Hz flash > power fail

Status: 

Backup mode

Always on

Status: System OK

Quick flashing

Critical Error

Status: output voltage too low
> UPS will be shut down

Status: Overcurrent detected
> UPS will be shut down

  

Summary of Contents for UPSI-2406DP1

Page 1: ...English User Manual UPSI 2406DP1 UPSI 2406DP2 Bicker Elektronik GmbH Ludwig Auer Straße 23 86609 Donauwörth Germany UPS SYSTEM DIN RAIL ...

Page 2: ...nded 16 07 2020 Revision 1 2 PELV indication removed 12 08 2020 Revision 1 3 Chapter B3 Intended use more detailed specified Chapter C1 Environmental conditions more detailed specified Indoor Outdoor Page 2 Warning Read User Manual at explanation Legend of used symbols supplemented Legend of used symbols Symbol Description Attention Important hazard warning This user manual has to be read before i...

Page 3: ...UPSI 2406DP1 UPSI 2406DP2 Revision 1 3 3 ...

Page 4: ... 3 5 kJ 0 972 Wh useful Ambient temperature Operating DP1 0 50 C DP2 20 65 C Storage Transport DP1 20 50 C DP2 30 65 C Operation altitude 4000 m Humidity 95 at 25 C no dew Dimensions W H D 63 x 120 x 100 mm 0 5 mm Weight 0 6 kg Technical Data A Brief specification UPSI 2406DP1 UPSI 2406DP2 24 VDC 4 A 24V DC UPS DIN rail version Integrated Li Ion batteries DP1 OR maintenance free Supercaps DP2 Cycl...

Page 5: ...lues apply to measurements at 25 C 0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Backup time UPSI 2406DP2 Nominal backup time vs Pout Backup time sek Output Power W 0 20 40 60 80 100 120 140 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 Backup time UPSI 2406DP1 Nominal backup time vs Pout Backup time min Output P...

Page 6: ... E1 Assembly and installation advice 17 E2 Convection and installation position 17 E3 Description of connectors 19 E4 Dimensioning the upstream power supply 20 E5 Initial operation 21 E6 Connecting diagram 22 E7 Overview connector Counterpart with part No Scope of delivery 23 E8 Charging time 23 E9 Reverse polarity Overload Short circuit 23 E10 Backup time 23 E11 Behavior in case of exceeding maxi...

Page 7: ...isconnecting the upstream source and also no voltage is measurable at the output the UPS can be still powered by the storage medium B3 Intended use Description This device is designed to be installed into a suitable enclosure which protects against electrical water and fire hazards and can then be used indoors and outdoors It is primary built for being mounted on a DIN Rail and is intended for pro...

Page 8: ...amaged devices into operation e g dents burn marks rough contamination 9 Keep ventilation openings clear 10 Do not drop the device 11 All parts of the device and accessories must not be eaten or swallowed 12 Use a current limited source for the UPS The required current values for the UPS are described in this manual 13 The UPS is powered by more than one source To shut down the UPS completely both...

Page 9: ...voltage Voltage drop Input Output 22 5 VDC 0 5 VDC max depending on load Current draw IN UN IOUT IN ICHARGE 0 IMAX UN IOUT ISTAT BOOST ICHARGE max INO LOAD UN IOUT 0 ICHARGE 0 ICHARGE UN IOUT 0 ICHARGE max 4 1 A 4 9 A 100 mA DP1 1 8 A DP2 1 5 A Power consumption PN UN IOUT IN ICHARGE 0 PMAX UN IOUT ISTAT BOOST ICHARGE max PCHARGE UN IOUT 0 ICHARGE max 98 4 W 117 6 W DP1 43 2 W DP2 36 W Internal in...

Page 10: ...OUT IN ICHARGE 0 PSTAT BOOST UN IOUT ISTAT BOOST ICHARGE 0 PDYN BOOST UN IOUT IDYN BOOST ICHARGE 0 96 W 99 W n a Short circuit proof Yes No load proof Yes OUTPUT DATA UPSI 2406DP1 UPSI 2406DP2 BACKUP MODE Unless otherwise stated all specifications apply to 25 C ambient temperature 24 V DC input voltage and nominal output current IN Output voltage 23 5 VDC Output voltage range n a Output current IN...

Page 11: ...06DP1 BP LIO 1525 Charging characteristic CC CV CP Nominal voltage UN 14 8 VDC End of charge voltage 15 9 VDC Charging current 1 C max Deep discharge protection 10 8 VDC Battery technology LIO Nominal capacity 2 5 Ah 37 Wh Charging time 80 min Buffer time IN 15 min ENERGY STORAGE UPSI 2406DP2 BP SUC 0835 Charging characteristic CC CV CP Nominal voltage UN 8 3 VDC End of charge voltage 8 3 VDC Char...

Page 12: ...nfigurable via Software Connection method Plug connection screwless Conductor cross section solid 0 205 mm 1 3 mm 24 16 AWG Conductor cross section flexible 0 205 mm 1 3 mm 24 16 AWG Conductor cross section with ferrule 0 205 mm 1 3 mm 24 16 AWG Stripping length 7 mm 9 mm DATA INTERFACE USB Interface designation USB Numbers of interfaces 1 Connection method USB type B female Locking No Transmissio...

Page 13: ... cable 1 1 Transmission length 10 m Access time 1 s Voltage level 5 VDC 5 VDC Electrical isolation No GENERAL DATA Flammability class according to UL 94 housing terminal blocks V0 Weight 0 6 kg UPS connection in parallel No UPS connection in series No LED status indicator Flashing interval 1 s HOUSING Degree of protection IP 20 Protection class III without PE Mounting type DIN Rail mounting Housin...

Page 14: ... height 4000 m Climate class 3k3 EN 60721 Degree of pollution 2 Overvoltage category EN 61010 1 EN 61010 2 201 I I Indoor Outdoor use Yes Yes in housing STANDARDS Protective extra low voltage IEC 61010 1 SELV IEC 61010 2 201 APPROVALS UL ETL UL61010 1 ETL UL61010 2 201 CSA CSA C22 2 61010 1 12 CSA C22 2 61010 2 201 CB Scheme IEC 61010 1 IEC 61010 2 201 Electromagnetic compatibility Conformity acco...

Page 15: ...ent 80 MHz 1 GHz 10 V m test level 3 1 4 GHz 2 GHz 3 V m test level 2 2 GHz 2 7 GHz 1 V m test level 1 Criterion A INTERFERENCE IMMUNITY ACCORDING TO EN 61000 6 2 INDUSTRY SECTOR Basic standard CE Normative minimum requirements EN 61000 6 2 CE Interference immunity of industrial environment Fast transients Burst EN 61000 4 4 Input Output Signal Comment 0 5 kV test level 1 symmetrical 0 5 kV test l...

Page 16: ... impairment of the operating behavior that is corrected by the device itself C2 Drawing UPSI 2406DP1 UPSI 2406DP2 120mm 63mm 9mm 44mm 100mm Tolerance 0 5 mm D Name Address Support E Mail Phone number of the manufacturer Bicker Elektronik GmbH Ludwig Auer Straße 23 86609 Donauwörth Germany E Mail support bicker de Tel 49 0 906 70595 0 ...

Page 17: ...Pay attention to correct polarity Before commissioning check all the connections for correctness E2 Convection and installation position Do not cover any ventilation holes by adjacent components For this DIN rail versions vertical mounting on a horizontal rail DIN rails according to EN 60715 is recommended in order to achieve the best possible convec tion of the UPS Another mounting position is po...

Page 18: ...UPSI 2406DP1 UPSI 2406DP2 Revision 1 3 18 DIN Rail mounting and DIN Rail profile according to EN 60715 2 3 4 1 Press down ...

Page 19: ...ON 1 Vin 2 Vin 3 Vout 4 Vout RS 232 PIN FUNCTION 1 NC 2 RXD 3 TXD 4 DTR 5 GND 6 DSR 7 NC 8 NC 9 NC RELAY CONNECTION RL Normally open contact NO When input power is interrupted the contact is closed 0Ω PIN FUNCTION 1 Relay contact 1 2 Relay contact 2 2 1 INPUT OUTPUT Vin Vout 4 3 2 1 ...

Page 20: ...om a SELV or PELV power supply In order to operate the UPSI devices to the maximum the upstream power supply has to provide at least the following output currents and voltages For UPSI 2406DP1 6A 24V For UPSI 2406DP2 6A 24V If less load than the maximum load is required at the output of the UPSI devices the voltage supply can be dimensioned according to the table below column 3 UPSI 2406DP1 UPSI 2...

Page 21: ...plied voltage at the input of the UPS is passed through to the output reduced by a current dependent voltage drop Vout Vin 0 5 V at maximum current The device charges the energy storage and monitors the upstream voltage thresholds at the input UPS function It must be ensured that the source supplies enough current to guarantee the charging process see also page 20 section E4 Dimensioning the upstr...

Page 22: ...l use D Sub 9 RELAY VOUT USB RS232 RL STATUS IN OUT UPSI DC UPS 120 mm 63 mm m VIN VOUT ATTENTION 1 Note polarity 2 AWG18 wire should be used 1 mm2 CONNECTING ORDER 1 APPLICATION VOUT 2 DC SOURCE VIN 3 RELAY USB RS232 Dismantling order reverse to connection E6 Connection ...

Page 23: ...he device is operating in backup mode reverse polarity protection not exists If the load current is too high for a duration longer than 3s the device switches off LED flashes quickly and continues oper ation automatically after 10s non latch In the event of a short circuit the output is immediately disconnected A start attempt is made every second non latch timer 1s The impact of a short circuit t...

Page 24: ... output and a lower voltage will appear at the output state 2s This condition should be avoided by shutting down the system in time before discharging the supercapacitors under high currents E12 Status LED 1 x flash pause 1 5s Status Battery start 2 x flash pause 1 5s Status Capacity for start is required state charging 3 x flash pause 1 5s Status shutdown Waiting for shutdown completion 4 x flash...

Page 25: ...e UPS and batteries should be placed within good air circulation The less deep the packs are discharged the longer the service life lasts E15 Maintenance The UPS contains no serviceable parts In case of a malfunction the upstream power source has to be discon nected and cables have to be removed Use a dry cloth for cleaning E16 Disposal Electric and electronic devices must not be disposed with dom...

Page 26: ...il could be caused With maximum load the voltage at the input of the device must not undercut 22 5V Even after the upstream supply has been disconnected the device continues to run for some time after the shortfall of the load sensor setting of a threshold value for current currents below this value will be classified as system off no load A short direct at the output of the device can cause damag...

Page 27: ...tions Windows is a registered trademark of the Microsoft Corp Status as at 12 08 2020 Revision 1 3 Bicker Elektronik GmbH Ludwig Auer Straße 23 86609 Donauwörth Germany Tel 49 0 906 70595 0 Fax 49 0 906 70595 55 E Mail info bicker de www bicker de ...

Reviews: