Input voltage
24 V DC (22.8…30 V)
Input current
11 A max.
Output voltage
Normal mode: V
IN
– 0.6 V DC max. (depending on load)
Battery mode: 23.5 V DC
Output current
10 A / 10.3…12 A for max. 10 s
Capacitive load
10 000 µF (at start / 0 A output load)
Charging method
CC / CV / CP
Protection
Interface
Possible battery technology
Ambient temperature
Operating altitude
Max. permitted humidity
Overcurrent protection at output
Short circuit protection at output
USB, RS232, HID
UPS
LiFePO4, Supercaps (EDLC)
Operating: -20…+70° C
Storage / Transport: -30…+70° C
≤4000 m
≤95 % (at +25° C, no dew)
Dimensions W/ H / D
137 x 20 x 100 mm ±0.5 mm
(including connectors and highest components)
Weight
0.125 kg
Technical Data
A Brief specification
UPSI-2412
24 V DC / 10 A
Powerful 24 V DC USV (Open Frame version)
Intelligent input current detection
Regulated output voltage in battery mode
Minimum load detection
Power-fail timer function
Relay dry contact on power fail
Reboot function
Fuel gauge
Batterie start function
Shutdown via external signal