A Technical Data
UPS-1000-B1
600 W / 1000 VA
Line Interactive Design mit Sinus-
Ausgangsspannung
AVR function (Buck / Boost)
Microprocessor-based controlling
Battery backup time monitoring
Operating temperature up to +60 °C
Reboot function
Load sensor
RS232 and USB interface for communication
with software UPSilon 2000
Hawker/Cyclon batteries
INPUT DATA
Input voltage
230 V AC
Input frequency
47 Hz ~ 65 Hz, 50/60 Hz, auto detection
Efficiency
App. 97 %, mains operation
Overcurrent protection
AC fuse 6.3 AT
Input voltage range
-20 % ~ +24 %
AVR range (2 Bucks, 2 Boosts)
Extended Buck: +15 % of selected nominal voltage
Buck mode: +8 % of selected nominal voltage
Boost mode: -8 % of selected nominal voltage
Extended Boost: -12.5 % of selected nominal voltage
Overvoltage protection
220 Joules