UPS-1000-B1
Revision 1
5
OUTPUT DATA
Output power at nominal inputs
600 W / 1000 VA max. at +40 °C
Derating
+40…+60 °C, 10 W / K
Output voltage
230 V AC
Voltage wave form
Sine
Crest factor
3:1
Output frequency (synchronised to mains)
Auto select for 50/60 Hz
47 Hz ~ 55 Hz for 50 Hz nominal;
56 Hz ~ 65 Hz for 60 Hz nominal
Transfer time
Blackout 3 ms typical, Brownout 1 ms,
battery mode to normal mode: 1 ms typical
Overload protection
Overload alarm level 100 % ~ 120 %,
Overload shutdown level 120 % ~ 190 %
BATTERY
Type of battery
1x BP-2480 (Cyclon), 24 V/ 8 Ah, 12 cells
Voltage
24 V DC
Typical backup time at half power
500 VA / 300 W: ca. 14 Min. bei +20 °C
Typical backup time at full power
1000 VA / 600 W: ca. 4.5 Min. bei +20 °C
Charging method
Smart puls charging with 2 charging modes:
Quick charging,
Trickle charging, at 90 % battery capacity
Charging time
App. 5 hours for 90 %, at 230 V AC and +25 °C
Charge current
2.5 A max.
Average charging voltage
Quick charging mode: 28.1 V max.
Trickle charging mode: 26.2 V…28.1 V
Protection
Thermal protection, overcurrent protection and
overcharging voltage protection
Summary of Contents for UPS-1000-B1
Page 3: ...UPS 1000 B1 Revision 1 3...