HR M
ANUAL
I
NSTALLATION
Manual version 3.0 (10-10-2017)
en-21
en
2.7
Connecting the unit to the building management system
The unit can be operated via a building management system.
Connect the unit to this.
• Feed a cable from the building management system to the
electronics module.
• Connect the cable to the electronics module
1
, in accord-
ance with the wiring diagram.
2.8
Installing the
b-touch
control panel (accessory)
2.8.1 Special points regarding the control panel
Positioning
• You can attach the control panel to the electronics mod-
ule, to the wall or to a standard junction box.
Cabling
Note:
n
Take the following into account, otherwise errors
may occur:
- The length of the control cable between the control
panel and the unit connected may not exceed 50 m.
- Keep control cables away from electromagnetic fields
and interference sources such as high-voltage cables
and fluorescent light starters.
- Lay control cables out straight or roll them in a bifi-
lar coil by folding cables in half before rolling them.
As a result, the magnetic fields will cancel each other
out to an important extent.
Note:
n
Use Biddle control cables only. Standard modular
telephone cable is NOT suitable.