HR M
ANUAL
O
PERATION
OF
THE
BUILDING
MANAGEMENT
SYSTEM
(BMS)
Manual version 3.0 (10-10-2017)
en-51
en
4.1.6 Alarm functions
In emergencies, the unit can emit an alarm signal or even
actively deal with the problem by functioning in a special
mode.
This special operation replaces the normal operation of the
unit (during the day and at night time) until the signal is no
longer active (435 is 0 again).
VALUE
OPTION
DESCRIPTION
ON
OFF
0
recirculation
(only functional in the case of units
with a recirculation module and in
manual control)
recirculation
(no heat recovery)
off
2
ventilation
(only functional in the case of units
with a recirculation module and in
manual control)
ventilation
(heat recovery from the
extracted air)
off
10
ventilation with night cooling
ventilation
(heat recovery from the
extracted air)
ventilation (fan speed 2)
(cooling with fresh air via by-
pass, no heat recovery)
REGISTER
ADDRESS
DESCRIPTION
RO
/
RW
*
CONTROL
UNIT
MINI
-
MUM
MAXI
-
MUM
DEFAULT
337
Alarm functions
(activated by input 1 (i1) or by
register address 435)
rw
-
0
41
0
435
Activate alarm functions (regis-
ter address 337)
0 = inactive
1 = active
rw
-
0
1
0
*ro = read only (read only)
*rw = read & write (read and write)