Technical Status: 11/2010 Page 3
Gas Detector
Operating and Installation Instructions
ExDetector HC 150 / HC 150-K
Connections
●
Max. lead length: 1000 m
●
Max. lead resistance: 12 ohm per conductor
Important Instructions
Never open the ExDetector housing in the presence of an explosive
atmosphere.
Terminal Assignment
●
Max. outside diameter of cable: 10 mm
●
Three-core cable with screen
●
Terminal assignment
24VDC
4-20 mA
GND
0,4-2V
Br
N
V
Br
4
5
6
1
2
3
KL 1
KL 2
KL 3
KL 4
KL 5
KL 6
power 24VDC SELV/PELV
output 4 ... 20 mA
GND
Sensor
Sensor
Sensor
Please note (when used without a Lang evaluator):
the power supply at KL 1 must be within the safe limits and have a
100 mA/T series fuse.