“ICON 2000v4"
instruction and operating manual
© Copyright by BIFFI Italia. All right reserved.
Section 618/42
Page 32
Contents may change without notice
Ext_User_Prm_Data_Const
(1)=0
Ext_User_Prm_Data_Const
(2)=0
Ext_User_Prm_Data_Ref
(3)=1
Ext_User_Prm_Data_Ref
(4)=2
Ext_User_Prm_Data_Ref
(5)=3
Ext_User_Prm_Data_Ref
(6)=4
Ext_User_Prm_Data_Ref
(7)=5
Ext_User_Prm_Data_Ref
(8)=7
Ext_User_Prm_Data_Ref
(9)=8
Ext_User_Prm_Data_Ref
(10)=9
Ext_User_Prm_Data_Ref
(11)=10
Ext_User_Prm_Data_Ref
(12)=6
Ext_User_Prm_Data_Ref
(13)=7
Ext_User_Prm_Data_Ref
(14)=8
Ext_User_Prm_Data_Ref
(15)=11
Ext_User_Prm_Data_Ref
(16)=12
Ext_User_Prm_Data_Const
(17)=0
Ext_User_Prm_Data_Ref
(18)=13
Ext_User_Prm_Data_Ref
(19)=14
;
;
Modular_Station
=1
Max_Module
=1
Max_Input_Len
=8
Max_Output_Len
=4
Max_Data_Len
=12
;
; Slave-Specification:
;
DPV1_Slave
=1
;
C1_Read_Write_supp
=0
C2_Read_Write_supp
=1
C2_Max_Data_Len
=240
C2_Response_Timeout
=100
C2_Read_Write_required
=0
C2_Max_Count_Channels
=3
Max_Initiate_PDU_Length
=72
Diagnostic_Alarm_supp
=0
Process_Alarm_supp
=0
Pull_Plug_Alarm_supp
=0
Status_Alarm_supp
=0
Update_Alarm_supp
=0
Manufacturer_Specific_Alarm_supp
=0
Extra_Alarm_SAP_supp
=0
Alarm_Sequence_Mode_Count
=0
Alarm_Type_Mode_supp
=0
Diagnostic_Alarm_required
=0
Process_Alarm_required
=0
Pull_Plug_Alarm_required
=0
Status_Alarm_required
=0
Update_Alarm_required
=0
Manufacturer_Specific_Alarm_required
=0
DPV1_Data_Types
=0
WD_Base_1ms_supp
=1
Check_Cfg_Mode
=0
;
;Device related Diagnosis
;
Unit_Diag_Bit
(24)=
"Motor Thermostat"
Unit_Diag_Bit
(25)=
"HI-HI Torque in Opening"
Unit_Diag_Bit
(26)=
"HI-HI Torque in Closing"
Unit_Diag_Bit
(27)=
"Actuator blocked in Opening"
Unit_Diag_Bit
(28)=
"Actuator blocked in Closing"
Unit_Diag_Bit
(29)=
"HI-HI Temperature"
Unit_Diag_Bit
(30)=
"Postition Sensor Failure"
Unit_Diag_Bit
(31)=
"Speed Sensor Failure"
Unit_Diag_Bit
(32)=
"Main Voltage Fault"
Unit_Diag_Bit
(33)=
"K1 Contactor Failure"
Unit_Diag_Bit
(34)=
"K2 Contactor Failure"
Unit_Diag_Bit
(35)=
"Configuration Error"
Unit_Diag_Bit
(36)=
"Hardware Error"
Unit_Diag_Bit
(37)=
"Low Alkaline Battery"
Unit_Diag_Bit
(38)=
"Lost Phase"
Unit_Diag_Bit
(39)=
"No response from base card"
;
; Module Definition List
Summary of Contents for ICON 2000
Page 1: ...2000 INSTRUCTION HANDBOOK MAN 618 MAN 618 MAN 618 ICON2000...
Page 2: ......
Page 115: ......